Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Heat pump air conditioners<br />
IDENTIFICATION<br />
TECHNICAL DATA<br />
PEGASUS.DX.A.P.O<br />
Heat pump air conditioning units with remote air cooled condenser suitable for comfort applications.<br />
Ductable air flow delivery from the top or direct delivery into the room through a plenum device.<br />
DNA@RC<br />
The large capacity precision air conditioning reliability transferred to “Comfort”<br />
applications all year long.<br />
PEGASUS.DX.A.P.O - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Heating capacity (2) kW<br />
Air flow m 3 /h<br />
Compressors n.<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Noise pressure level (3) dB(A)<br />
PEGASUS.DX.A.P.O - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Heating capacity (2) kW<br />
Air flow m 3 /h<br />
Compressors n.<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Noise pressure level (3) dB(A)<br />
5.Z1 7.Z1 10.Z1 15.Z1 18.Z1 20.Z1 24.Z2<br />
S0 S0 S1 S1 S2 S4 S5<br />
6,3 7,4 11,4 15,3 18 21,8 25,6<br />
5,7 6,7 10,3 14,2 16,5 19,4 22,1<br />
1580 1580 3150 3150 3640 5570 6000<br />
1 1 1 1 1 1 2<br />
645 645 645 645 755 1105 1125<br />
410 410 645 645 645 645 860<br />
1680 1680 1930 1930 1930 1930 1950<br />
145 150 205 210 235 265 380<br />
51,5 51,5 52 52 54 54,5 55,6<br />
30.Z2 36.Z2 40.Z2 52.Z2 60.Z2 74.Z2 88.Z2<br />
S5 S6 S7 S8 S9 S9 S9<br />
29,2 35,9 40,2 52,5 63 76,2 86<br />
26,7 33 35,6 45,8 53,5 73,7 83,9<br />
6000 8200 10400 13500 17000 17000 17000<br />
2 2 2 2 2 2 2<br />
1125 1360 1750 2210 2680 2680 2680<br />
860 860 860 860 860 860 860<br />
1950 1950 1950 1950 1950 1950 1950<br />
385 460 615 840 1000 1020 1050<br />
55,6 58 59 60 62,5 62,5 62,5<br />
(1) Characteristics referred to evaporator air inlet at 27°C with 47% rH; condenser air inlet at 35°C.<br />
(2) Characteristics referred to air inlet at 20°C, outdoor air at 7°C with 87% rH.<br />
(3) Noise pressure 1m far from the unit in free field conditions with ducted air distribution.<br />
POWER SUPPLY: 230.1.50 for models 5.Z.1 and 7.Z.1 • 400.3.50+Mp for other models<br />