Free-cooling liquid chillers with axial fans<br />

TECHNICAL DATA IDENTIFICATION<br />

MAXIMO.RECIP.A.STD “G”<br />

Air cooled packaged liquid chillers equipped with energy saving free-cooling SCR system, reciprocating<br />

compressors and axial fans. Casing type: “G”.<br />

SCR&MP99 (RC GROUP free-cooling system)<br />

MAXIMO chillers control system is based on a RC proprietary software and it is the sum of RC experiences achieved<br />

through thousand of installations all over the world, from Siberia to South Africa, from Buenos Aires to Beijing through<br />

Madrid and London.<br />

The possibility to test SCR system directly in numerous and different climatic situations and in various application fields<br />

(precision and comfort air conditioning, industrial and process cooling for chemical, pharmaceutical, food and mechanical<br />

industry) allowed RC to develop a specific know-how which is not easily achievable by other companies working in the<br />

same field.<br />

This solution brings energy savings that cannot be matched by competitors equipment.<br />

MAXIMO.RECIP.A.STD “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

MAXIMO.RECIP.A.STD “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

142.F2 188.F2 220.F2 260.F2 300.F2<br />

G7 G8 G8 G8 G8<br />

146,2 183,1 216,4 259,5 285,7<br />

117,2 173,6 213,2 220 223,1<br />

2 2 2 2 2<br />

2 2 2 2 2<br />

3600 5170 5170 5170 5170<br />

1560 1590 1590 1590 1590<br />

2115 2155 2155 2215 2215<br />

2095 2310 2465 2830 2860<br />

66 66 67 73 73<br />

320.S2 350.F2 385.S2 440.S2<br />

G9 G9 G9 G9<br />

325,9 354,8 377,2 412,1<br />

254,8 257,8 274,6 275,8<br />

2 2 2 2<br />

2 2 2 2<br />

5900 5900 5900 5900<br />

2070 2070 2070 2070<br />

2470 2470 2470 2470<br />

5130 4430 5170 5180<br />

72 72 72 72<br />

(1) Data referred to chilled water temperature at 15/10°C; outdoor air temperature at 35°C.<br />

(2) Data referred to inlet chilled water temperature at 15°C; outdoor air temperature at 2,5°C.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

144 RC GROUP SpA • General Catalogue• 155.EN.0504