08.12.2012 Views

g e n e r a l catalogue - perago.sk

g e n e r a l catalogue - perago.sk

g e n e r a l catalogue - perago.sk

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Free-cooling liquid chillers with axial fans<br />

TECHNICAL DATA IDENTIFICATION<br />

MAXIMO.RECIP.A.STD “U”<br />

Air cooled packaged liquid chillers equipped with energy saving free-cooling SCR system, reciprocating<br />

compressors and axial fans. Casing type: “U”.<br />

Optimizer®<br />

MAXIMO.RECIP.A.STD “U” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

MAXIMO.RECIP.A.STD “U” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

Patent<br />

RC Group, once again, has been the first company of its field to manufacture free-cooling chillers up to 1.000 Kw. The<br />

leadership in this market segment is confirmed by a large number of units of this size installed in the last years all over<br />

Europe.<br />

Thanks to the experience reached gradually in these “huge” installations, RC designed and patented a new system to<br />

extend SCR free-cooling system use also in temperate climate areas or to increase the energy savings in cold areas.<br />

The so called OPTIMIZER system is composed by a set of innovations at a hydraulic connections and control software<br />

level. OPTIMIZER is internationally patented.<br />

495.S2 550.S2 600.S2 660.S2<br />

U10 U10 U11 U11<br />

484 522 597,4 635,9<br />

376,5 380,5 472,9 476,9<br />

2 2 2 2<br />

2 2 2 2<br />

5500 5500 6490 6490<br />

2385 2385 2385 2385<br />

2430 2430 2430 2430<br />

5430 5440 6500 6500<br />

75 75 75 75<br />

770.S2 880.S2 990.S2 1100.S2<br />

U12 U13 U14 U14<br />

746 848,7 968,6 1040,5<br />

561,3 655,5 753,1 756,9<br />

2 2 2 2<br />

2 2 2 2<br />

7480 8470 9460 9460<br />

2385 2385 2385 2385<br />

2430 2430 2430 2430<br />

7860 8840 9310 9320<br />

76 77 77 77<br />

(1) Data referred to chilled water temperature at 15/10°C; outdoor air temperature at 35°C.<br />

(2) Data referred to inlet chilled water temperature at 15°C; outdoor air temperature at 2,5°C.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

148 RC GROUP SpA • General Catalogue• 155.EN.0504

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!