Free-cooling liquid chillers with axial fans<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

MAXIMO.SCREW.A.STD “W”<br />

Air cooled packaged liquid chillers equipped with energy saving free-cooling SCR system, screw compressors<br />

and axial fans. Casing type: “W”.<br />

RCProactive<br />

MAXIMO W, a range of chillers equipped with SCR system and supplying up to 1.650 Kw for a single unit and with last<br />

generation SCREW compressors. Also MAXIMO W is equipped with RESTART proprietary software.<br />

In case of a restart after a possible stop of the units due to a blackout, this particular system activates a restart<br />

procedure granting the chiller in operation even with a return water high temperature. Usually this situation would cause<br />

an immediate stop of the chiller (complete stop with manual restart need) for high pressure. RESTART is vital in all those<br />

plants with high thermal load and low inertia, where even a few minutes of energy loss (usually time needed for diesel<br />

generator start-up) would increase the water temperature in excess of that possible for any other chiller to start without<br />

the RESTART system.<br />

MAXIMO.SCREW.A.STD “W” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

1260.V3 1410.V3 1500.V3 1650.V3<br />

W21 W22 W23 W23<br />

1399,3 1525,9 1671,9 1869,3<br />

1088,6 1196 1333 1332,5<br />

3 3 3 3<br />

3 3 3 3<br />

10800 11870 12940 12940<br />

2350 2350 2350 2350<br />

2610 2610 2610 2610<br />

13830 15000 16100 16250<br />

84 84 84 84<br />

(1) Data referred to chilled water temperature at 15/10°C; outdoor air temperature at 35°C.<br />

(2) Data referred to inlet chilled water temperature at 15°C; outdoor air temperature at 2,5°C.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

162 RC GROUP SpA • General Catalogue• 155.EN.0504