Free-cooling liquid chillers with axial fans<br />

TECHNICAL DATA IDENTIFICATION<br />

MAXIMO.SCREW.A.ELN “G”<br />

Air cooled packaged liquid chillers in extremely low noise version equipped with energy saving free-cooling<br />

SCR system, screw compressors and axial fans. Casing type: “G”.<br />

AntiRumble<br />

Highest energy saving and lowest noise emission together in the same product.<br />

MAXIMO SCREW ELN exploits the typical low vibration operation of screw compressors to obtain a high<br />

performing product at noise reduction level.<br />

The unit base frame is realised with ANTIRUMBLE system and is made of a multiple layer structure with high<br />

noise absorption characteristics, thus allowing the keeping of a high noise efficiency even in cases where the<br />

units are installed in a “raised” position through weight distribution bars and/or antivibration holders.<br />

MAXIMO.SCREW.A.ELN “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

MAXIMO.SCREW.A.ELN “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

230.V1 280.V1<br />

G9 G9<br />

261,4 300,2<br />

255,6 252,8<br />

1 1<br />

1 1<br />

5900 5900<br />

2070 2070<br />

2470 2470<br />

4175 4255<br />

59 59<br />

200.V2 240.V2 280.V2<br />

G8 G9 G9<br />

208,3 271,9 295,7<br />

185,8 255,7 250<br />

2 2 2<br />

2 2 2<br />

5170 5900 5900<br />

1590 2070 2070<br />

2155 2470 2470<br />

2860 4220 4245<br />

55 60 69<br />

(1) Data referred to chilled water temperature at 15/10°C; outdoor air temperature at 35°C.<br />

(2) Data referred to inlet chilled water temperature at 15°C; outdoor air temperature at 2,5°C.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />