Air conditioners for information technology<br />

and communication - DISPLACEMENT<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

PEGASUS.CW.DL<br />

Chilled water feeding air conditioning unit suitable for hi-tech. facilities or telecom exchanges.<br />

Air flow from the front and from the side through a grille for displacement air distribution.<br />

Thanks to “kit under” optional it is possible to convert the unit into a downflow air conditioning unit (under).<br />

PerformancePlus<br />

Displacement air distribution system grants an optimal temperatures stratification in the room<br />

assuring the maximum possible thermodynamic efficiency in every situation.<br />

PEGASUS.CW.DL - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Cooling capacity (2) kW<br />

Air flow m 3 /h<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Noise pressure level (3) dB(A)<br />

8 11 22 35 48<br />

S2/S S2 S4 S7/S S8/S<br />

11,4 15 28,8 45,7 61,5<br />

8,3 11,2 21,3 33,6 45,3<br />

1500 2450 4650 7250 9800<br />

755 755 1105 1720 2180<br />

645 645 645 645 645<br />

1930 1930 1930 1930 1930<br />

175 180 200 295 370<br />

48 54 56,5 58 59<br />

(1) Performance referred to room conditions at 1m from floor at 24°C with 50% rH, deriving from the air conditioner air temperature inlet at 30°C with 35% rH; chilled water inlet at 7°C.<br />

(2) Performance referred to room conditions at 1m from floor at 24°C with 50% rH, deriving from the air conditioner air temperature inlet at 30°C with 35% rH; chilled water inlet at 10°C.<br />

(3) Noise pressure 1m far from the unit in free filed conditions.<br />

POWER SUPPLY:<br />

The units in only cooling version are directly supplied by the UPS system at 230 Vac or 48Vdc<br />

For the units in cooling + heating version it is necessary to connect also the 400.3.50+N network supply.<br />

86 RC GROUP SpA • General Catalogue• 155.EN.0504