Multifunction liquid chillers with centrifugal fans<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

MULTIPLO.SCROLL.C.P.ELN “G”<br />

Multifunction air cooled packaged liquid chillers in extremely low noise version equipped with Scroll<br />

compressors and centrifugal fans. Casing type: ”G”.<br />

ELN Range (Extremely Low Noise)<br />

Over 20 years of experience in sound reduction techniques together with SCROLL technology enable RC Group to grant excellent<br />

sound emission levels for this equipment.<br />

These top sound levels are the result of a specific design philosophy concentrated on removing the sound emissions at "source",<br />

without using "bolt-on" acoustic kits.<br />

The use of the latest generation SCROLL compressors highlights the ELN range of characteristics making plant selection of critical<br />

acoustic systems easy.<br />

MULTIPLO.SCROLL.C.ELN “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Heating capacity (2) kW<br />

Cooling capacity (3) kW<br />

Heating capacity (3) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

64.Z2 74.Z2 100.Z2 124.Z2<br />

G7 G7 G8 G8<br />

55,1 63,3 87,8 109,3<br />

69,3 81,6 108 135,4<br />

59,5 69,4 94,6 114,9<br />

81,5 94,5 129,7 158,9<br />

2 2 2 2<br />

2 2 2 2<br />

3600 3600 5170 5170<br />

1290 1290 1290 1290<br />

2010 2010 2050 2050<br />

1400 1330 2065 2085<br />

64 66 58 62<br />

(1) Only cooling: Data referred to outlet chilled water temperature at 7°C; air to condenser at 35°C.<br />

(2) Only heating: Data referred to hot water temperature at 40/45°C; air to gas/air heat exchanger at 7°C with 90%RH.<br />

(3) Cooling and heating: Data referred to outlet chilled water temperature at 7°C; hot water temperature 40/45°C<br />

Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

230 RC GROUP SpA • General Catalogue• 155.EN.0504