Heat pump liquid chillers with axial fans<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

REVERSO.RECIP.A.P.STD “U”<br />

Heat pump air cooled packaged liquid chillers equipped with reciprocating compressors and axial fans.<br />

Casing type: “U”.<br />

REVERSO “U” range includes heat pump liquid chillers up to 1.000 kW capacity, among the biggest available on the market<br />

today. This allows to considerably reduce spaces and hydraulic and electrical connections in large air conditioning<br />

systems.<br />

This solution grants high installation and management savings. Moreover, the reduced number of compressors/fans used to<br />

achieve these capacities decreases the ri<strong>sk</strong> rate usually considered as directly proportional to the number of moving<br />

parts. RC is among the world leaders in this specific field, with hundred of installations realised with REVERSO liquid<br />

chillers of capacity between 750 and 1.000 kW, indeed an experience hardly comparable.<br />

REVERSO.RECIP.A.P.STD “U” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Heating capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

REVERSO.RECIP.A.P.STD “U” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Heating capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

495.S2 550.S2 600.S2 660.S2<br />

U10 U10 U11 U11<br />

456,2 491,5 553,2 588<br />

501,9 542,1 612 650,2<br />

2 2 2 2<br />

2 2 2 2<br />

5500 5500 6490 6490<br />

2130 2130 2130 2130<br />

2430 2430 2430 2430<br />

5114 5119 5700 5700<br />

76 76 76 76<br />

770.S2 880.S2 990.S2 1100.S2<br />

U13 U13 U14 U14<br />

714,9 795,5 901 976,6<br />

794 882,6 995,6 1075,7<br />

2 2 2 2<br />

2 2 2 2<br />

8470 8470 9460 9460<br />

2130 2130 2130 2130<br />

2430 2430 2430 2430<br />

7051 7216 7892 7897<br />

78 78 78 78<br />

(1) Data referred to outlet chilled water temperature at 7°C; air to condenser at 35°C.<br />

(2) Data referred to hot water temperature at 40/45°C; air to gas/air heat exchanger at 7°C with 90%RH.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

192 RC GROUP SpA • General Catalogue• 155.EN.0504