Free-cooling liquid chillers with axial fans<br />
TECHNICAL DATA IDENTIFICATION<br />
MAXIMO.SCROLL.A.ELN “G”<br />
Air cooled packaged liquid chillers in extremely low noise version equipped with energy saving free-cooling<br />
SCR system, Scroll compressors and axial fans. Casing type: “G”.<br />
ELN Range (Extremely low noise)<br />
For over 20 years RC Group has offered a complete range of units designed specifically to provide the "lowest noise<br />
emission" equipment on the market.<br />
The design and continuous development of the ELN range has avoided using "bolt-on" acoustic kits, adding weight and<br />
reducing the serviceability of the equipment but instead has concentrated on removing the sound emissions at "source".<br />
This one solution grants : high efficiency, extremely low sound emissions and easy maintenance, no need to remove heavy<br />
noise reduction kits or acoustic barriers. The performance and durability of the RC Group solution lasts with time, unlike<br />
that of the materials of the "bolt-on" sound reduction kits that can decay over time.<br />
MAXIMO.SCROLL.A.ELN “G” - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Free-Cooling capacity (2) kW<br />
Compressors n.<br />
Gas circuits n.<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Mean sound pressure level (3) dB(A)<br />
MAXIMO.SCROLL.A.ELN “G” - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Free-Cooling capacity (2) kW<br />
Compressors n.<br />
Gas circuits n.<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Mean sound pressure level (3) dB(A)<br />
21.Z1 25.Z1 32.Z1 37.Z1 50.Z1 61.Z1<br />
G2 G2 G4 G4 G5 G5<br />
22,2 24,6 32,1 38,4 52,7 61,5<br />
23 23,4 29,9 36,8 52,5 53,9<br />
1 1 1 1 1 1<br />
1 1 1 1 1 1<br />
2000 2000 2600 2600 2600 2600<br />
1250 1250 1410 1410 1410 1410<br />
1690 1690 1690 1690 2240 2240<br />
545 545 750 800 1090 1095<br />
51 51 55 52 55 55<br />
36.Z2 42.Z2 50.Z2 64.Z2 74.Z2 87.Z2 100.Z2 124.Z2<br />
G4 G4 G5 G7 G7 G7 G7 G8<br />
36 42,8 50,1 63,4 74,6 90,1 99,4 120,1<br />
36,3 41,1 52 62,5 77,8 87,6 89,1 120,2<br />
2 2 2 2 2 2 2 2<br />
2 2 2 2 2 2 2 2<br />
2600 2600 2600 3600 3600 3600 3600 5170<br />
1410 1410 1410 1560 1560 1560 1560 1590<br />
1690 1690 2240 2215 2215 2215 2215 2155<br />
890 910 1080 1430 1550 1650 1710 2070<br />
52 55 55 51 55 51 51 53<br />
(1) Data referred to chilled water temperature at 15/10°C; outdoor air temperature at 35°C.<br />
(2) Data referred to inlet chilled water temperature at 15°C; outdoor air temperature at 2,5°C.<br />
(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />
POWER SUPPLY: 400.3.50+N<br />
142 RC GROUP SpA • General Catalogue• 155.EN.0504