Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Close control air conditioners with<br />
Displacement air delivery<br />
IDENTIFICATION<br />
TECHNICAL DATA<br />
HEAT HUNTER.CW<br />
Chilled water feeding air conditioning units, suitable for hi-tech. facilities applications and and telecom exchanges.<br />
Displacement mode air delivery for air distribution directly into the room.<br />
Synergy<br />
The Heat Hunter system can be used to increase the capacity of existing plants, in perfect synergy<br />
with traditional machines.<br />
HEAT HUNTER.CW - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Cooling capacity (2) kW<br />
Cooling capacity (3) kW<br />
Cooling capacity (4) kW<br />
Cooling capacity (5) kW<br />
Cooling capacity (6) kW<br />
Air flow m 3 /h<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Noise pressure level (7) dB(A)<br />
014 021 025 044 066<br />
HH0 HH1 HH1 HH2 HH3<br />
10,9 17,9 25,0 34,2 49,7<br />
12,6 20,7 29,0 39,5 57,5<br />
14,2 23,1 32,5 44,2 64,4<br />
8,1 13,5 18,2 22,9 36,9<br />
9,8 16,3 22,2 28,2 44,8<br />
11,4 18,8 25,9 33,6 51,7<br />
2200 3330 5500 6660 10000<br />
785 1470 1470 2005 2540<br />
600 600 600 600 600<br />
1980 1980 1980 1980 1980<br />
165 270 290 355 435<br />
45,5 49,0 50,0 52,0 53,5<br />
(1) Characteristics referred to air inlet at 24°C with 50% rH; chilled water temperature 7/12°C - 0% glycol solution.<br />
(2) Characteristics referred to air inlet at 27°C with 42% rH; chilled water temperature 7/12°C - 0% glycol solution.<br />
(3) Characteristics referred to air inlet at 30°C with 35% rH; chilled water temperature 7/12°C - 0% glycol solution.<br />
(4) Characteristics referred to air inlet at 24°C with 50% rH; chilled water temperature 9/14°C - 0% glycol solution.<br />
(5) Characteristics referred to air inlet at 27°C with 42% rH; chilled water temperature 9/14°C - 0% glycol solution.<br />
(6) Characteristics referred to air inlet at 30°C with 35% rH; chilled water temperature 9/14°C - 0% glycol solution.<br />
(7) Radiated noise pressure 1m far from the unit in free field conditions.<br />
POWER SUPPLY: 400.3.50+Mp<br />
58 RC GROUP SpA • General Catalogue • 155.EN.0504