08.12.2012 Views

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1-1 Unit Specifications<br />

4-Way Air Discharge Semi-concealed Type<br />

1. Specifications<br />

MODEL No. Indoor Unit ASR 448 H<br />

Outdoor Unit AER 448 SCL3E<br />

POWER SOURCE 380 - 400 - 415 V / 3N / 50 Hz<br />

PERFORMANCE Cooling<br />

Capacity kW 12.6<br />

BTU / h 43,000<br />

Air circulation (Hi / Me / Lo) m3 /h 1,920 / 1,680 / 1,320<br />

Moisture removal (High)<br />

ELECTRICAL RATINGS<br />

Liters/h 6.3<br />

Voltage rating V 380 400 415<br />

Available voltage range V 342 – 456<br />

Running amperes* A 8.35 8.35 8.37<br />

Max. running amperes** A 9.47 9.47 9.49<br />

Power input kW 4.6 4.64 4.67<br />

C.O.P W / W 2.74 2.72 2.70<br />

Max. starting amperes<br />

FEATURES<br />

A 53 56 58<br />

Controls / Thermostat control Microprocessor / I.C. thermostat<br />

Timer ON / OFF 72-hours ON/OFF 24-hours & Program<br />

Fan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)<br />

Airflow direction (Indoor) Automatic (Remote control)<br />

Air filter Washable, easy access, long life (2,500 hr)<br />

Remote controller (Option) Wired : REM HW A Wireless : REM CLR A<br />

Refrigerant control Electronic expansion valve<br />

Drain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)<br />

Compressor Scroll (Sanyo)<br />

Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36<br />

Outdoor - Hi dB - A 55<br />

Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL<br />

REFRIGERANT TUBING<br />

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GL<br />

Limit of tubing length m (ft.) 50 (164 )<br />

Limit of tubing length at shipment m (ft.) 30 ( 98 )<br />

Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)<br />

between the two units Outdoor unit is lower than indoor unit : 30 (98)<br />

Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)<br />

outer diameter Wide tube mm (in.) 19.05 (3 / 4)<br />

Refrigerant amount at shipment kg R407C - 4.5<br />

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unit<br />

Unit dimensions Height mm (in.) 358 ( 14 - 3 / 32) 1,235 (48 - 20 / 32)<br />

Width mm (in.) 1,150 ( 45 - 9 / 32) 940 (37 )<br />

Depth mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32)<br />

Package dimensions Body : SASR 448 H Panel : ASG 3648 Outdoor unit<br />

Height mm (in.) 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32)<br />

Width mm (in.) 1,114 (43 - 27 / 32) 1,257 (49 - 16 / 32) 1,016 (40 )<br />

Depth mm (in.) 860 (33 - 27 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32)<br />

Net weight kg (lb.) 38 (84) 106 ( 234)<br />

Shipping weight kg (lb.) 32 ( 71 ) 10 ( 22) 113 ( 249 )<br />

Shipping volume m3 (cu. ft) 0.303 (10.7) 0.131 ( 4.6) 0.56 (19.8)<br />

DATA SUBJECT TO CHANGE WITHOUT NOTICE.<br />

Cooling:<br />

Rating conditions (*): Indoor air temperature 27 °C DB/19 °C WB, Outdoor air temperature 35 °C DB<br />

Full load conditions (**): Indoor air temperature 32 °C DB/23 °C WB, Outdoor air temperature 43 °C DB<br />

I - 5<br />

1<br />

2<br />

3<br />

4<br />

5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!