4. Service procedures<br />
6 Solenoid coil of the electronic refrigerant<br />
control valve (ERCV) ………… Indoor unit<br />
*Measure the coil resistance.<br />
• Measure the resistance between No. 5 (GRY lead wire) and other terminals<br />
(another color of lead wires) of 5P (WHT) plug connected to the solenoid coil.<br />
Refer to “1-2-(A) Major component specifications”.<br />
7 Compressor motor (CM) ……… Outdoor unit *Measure the coil resistance.<br />
• In case of triple -phase compressor<br />
Measure the resistance between “R” (RED lead wire) and “S” (WHT lead<br />
wire) terminals, “R” and “T” (BLU lead wire) terminals and “S” and “T”<br />
terminals on the compressor motor magnetic contactor.<br />
• In case of single -phase compressor<br />
Remove the cover of compressor terminal and measure the resistance<br />
between terminals.<br />
Refer to “1-2 Major component specifications”.<br />
8 Compressor motor magnetic contactor (52C) ………… Outdoor unit<br />
• Measure the resistance between A (ORG lead wire) and B (GRY lead wire)<br />
terminals on the compressor motor magnetic contactor.<br />
Refer to “1-3 Other component specifications”.<br />
• Check the continuity between contactors.<br />
MODEL<br />
Push button on<br />
the magnetic<br />
contactor<br />
no press<br />
press<br />
FMCA–1S / FC–1SZ607<br />
Pair of terminals<br />
R – U S – V T – W 31 – 32<br />
–––– –––– –––– YES<br />
YES YES YES ––––<br />
9 Solenoid coil of 4-way valve (20S) … Outdoor unit<br />
*Measure the coil resistance.<br />
• Measure the resistance between No.1 (BLU lead wire) and No.2 (BLU lead<br />
wire) terminals of 2P (YEL) socket connected to the solenoid coil.<br />
Refer “1-3 Other component specifications”.