(C) Check the sensor temperature readings<br />

The air conditioner has thermo sensors which are used to control the unit.<br />

IV - 24<br />

4. Service procedures<br />

❏ Each sensor has an address which is made up of the indoor unit address, and the<br />

sensor address. The indoor unit address is used only when several units are<br />

hooked up to one remote controller (group control). If there is only one unit, made<br />

up of one indoor and one outdoor unit, then only the sensor address should be put<br />

in, as shown in the procedure below.<br />

Follow this procedure to display the temperature of each sensor:<br />

a On the remote controller, press both TEST / CHK and CL buttons at the same time for<br />

more than 4 seconds.<br />

AIR FLOW<br />

UNIT<br />

FLAP<br />

TIMER SET<br />

SET CL<br />

A<br />

UNIT No.<br />

R.C. No.<br />

AIM<br />

CODE No.<br />

°C<br />

SWEEP<br />

SET TEMP.<br />

SETTING<br />

b The UNIT No., the address and temperature of the sensors instead of its usual<br />

information will flash on the display.<br />

ON •<br />

OFF •<br />

❏ Following example shows the UNIT No. (Indoor unit address) is fixed at 01– 01.<br />

❑ In case of group control, select the UNIT NO. (Indoor unit address) which you want<br />

to check with UNIT button.<br />

❏ Each time you press the , (SET TEMP.) button you can select a different<br />

sensor, and the display shows the sensor address and temperature as shown<br />

below.<br />

NOTE<br />

AIR FLOW<br />

UNIT<br />

FLAP<br />

TIMER SET<br />

SET CL<br />

UNIT No.<br />

R.C. No.<br />

MONITOR<br />

CODE No.<br />

SETTING<br />

DATA<br />

ON •<br />

OFF •<br />

MODE<br />

SET TEMP.<br />

FAN SPEED<br />

TEST / CHK<br />

MODE<br />

SET TEMP.<br />

FAN SPEED<br />

TEST / CHK<br />

0356_M_I<br />

Do not press TIMER SET button during the procedure.<br />

UNIT No. (Indoor unit address)<br />

Sensor address<br />

Sensor temperature °C<br />

0357_M_I