4. Service procedures<br />

6) Symptom: LCD on the remote controller is displaying “CHECK E06”. (Unusual<br />

communication between the indoor and outdoor units)<br />

Start<br />

Is there a cut line or contact<br />

defect between an indoor and<br />

outdoor unit’s control line?<br />

* See the section of INSTALLATION INSTRUCTION concerning with flexible<br />

combination system.<br />

7) Symptom: LCD on the remote controller is displaying “CHECK E08”. (Duplicate<br />

indoor unit address setting)<br />

Start<br />

No<br />

Influenced by external noise<br />

Start<br />

Is the setting for the non-volatile<br />

memory IC on the indoor unit PCB<br />

inappropriate?<br />

(Are there two units with the same<br />

address?)<br />

No<br />

Influenced by external noise<br />

Are there two remote controllers<br />

(master-slave) installed with both<br />

remote controllers set as masters?<br />

No<br />

Replace the remote controller.<br />

Yes<br />

Yes<br />

8) Symptom: LCD on the remote controller is displaying “CHECK E09”. (Duplicate<br />

setting of RCU address switch of remote controllers)<br />

Yes<br />

IV - 13<br />

Correct wiring.<br />

Correct the setting.<br />

Correct the setting.<br />

* See the section of INSTALLATION INSTRUCTION concerning with controlling<br />

remote controller switches when there are two remote controllers.<br />

1903_M_I<br />

1904_M_I<br />

* See the section of INSTALLATION INSTRUCTION concerning with flexible<br />

combination system.<br />

0339_M_I<br />

*<br />

1<br />

2<br />

3<br />

4<br />

5