1<br />

12<br />

3<br />

4<br />

5<br />

15) Symptom: LCD on the remote controller displays “CHECK E16”.<br />

Start<br />

When the group of the units are<br />

installed, is there any mis-cross<br />

between inter unit control wiring and<br />

refrigerant tubing?<br />

No<br />

Are the total capacities of indoor units<br />

to that of outdoor units more than 107%?<br />

No<br />

Confirm less than 5 indoor units are<br />

connected.<br />

No<br />

Yes<br />

Yes<br />

IV - 18<br />

Repair the wiring.<br />

Select indoor units which match with<br />

the outdoor capacity.<br />

16) “Check P9” is displayed on the remote control unit.<br />

Start<br />

Is 15P connector socket (RED)<br />

being attached to panel<br />

connected firmly with 15P plug?<br />

Yes<br />

Replace P.C.B. Ass’y in the<br />

indoor unit.<br />

Yes<br />

Connect firmly.<br />

0649_M_S<br />

0647_M_S<br />

4. Service procedures