Cables for Installations and Industry - Draka
Cables for Installations and Industry - Draka
Cables for Installations and Industry - Draka
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
INSTALLATION CABLES<br />
14<br />
N<br />
AP PLI CA TION<br />
For fixed sur face in stal la tion in doors.<br />
Cur rent car ry ing ca paci ties ac cord ing to HD 384.5.523<br />
(or IEC 364- 5- 523): “Elec tri cal in stal la tion of build ings”<br />
-se ction 523: Cur rent car ry ing ca paci ties.<br />
Maxi mum per mis si ble tem pera ture of con duc tor:<br />
- in con tinu ous use +70 °C<br />
- in a short cir cuit (max. 5 s) +160 °C<br />
Low est rec om mended han dling<br />
tem pera ture: –15 °C<br />
Mini mum rec om mended bend ing ra dius:<br />
- dur ing in stal la tion 10xD<br />
- in a fi nal in stal la tion if bent only once 3xD<br />
Maxi mum per mis si ble ten sile stress<br />
dur ing in stal la tion Ax50 N/mm²<br />
CON STRUC TION<br />
Con duc tor An nealed cop per wire<br />
In su la tion PVC, core iden ti fi ca tion by col ours<br />
Fill ing Fill ing com pound<br />
Surfa ce instal la ti on cab le NOT KA<br />
MPLM<br />
WITH PROTECTIVE CONDUCTOR<br />
RATED VOLT AGE<br />
U o /U = 300/500 V<br />
STAN DARD<br />
SS 424 02 19-2<br />
CORE IDEN TI FI CA TION<br />
Self- extinguishing IEC 332-1<br />
Drain wire Tinned copper wires<br />
Metal sheath Lon gi tu di nal alu min ium tape<br />
Sheath White PVC<br />
WITHOUT<br />
PROTECTIVE<br />
CONDUCTOR<br />
Number of conductors <strong>and</strong><br />
cross-section nxmm² 3 x 1,5/1 S 3 x 2,5/1 S 4 x 1,5/1 S 5 x 1,5/1 S 2 x 1,5/1 N 3 x 1,5/1 N<br />
EAN code (SSTL code) 64 100+ 04 055 26-7 04 055 27-4 04 055 36-6 04 055 46-5 04 055 11-3 04 055 23-6<br />
Nominal overall diameter mm 8,5 9,8 9,2 10,0 8,0 8,5<br />
Total weight kg/km 130 185 165 185 110 130<br />
Direct current resistance of<br />
conductor at +20 °C.max. Ω/km 12,1 7,41 12,1 12,1 12,1 12,1<br />
St<strong>and</strong>ard delivery length<br />
coil m 50 50 50 50 50 50<br />
2-wires<br />
3-wires<br />
N-system S-ystem<br />
3-wires<br />
4-wires<br />
5-wires