Cables for Installations and Industry - Draka
Cables for Installations and Industry - Draka
Cables for Installations and Industry - Draka
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
AP PLI CA TIONS<br />
— Fixed in door — Alarm, sig nal <strong>and</strong><br />
in stal la tions se cu rity con trol<br />
— Build ing auto ma tion trans mis sion<br />
Maxi mum ambient tem pera ture:<br />
- in operation +70 °C<br />
Low est rec om mended installation<br />
tem pera ture: –5 °C<br />
Mini mum rec om mended bend ing ra dius:<br />
- dur ing in stal la tion 15xD<br />
- during operation 10xD<br />
CON STRUC TION<br />
Ac cord ing to SFS 2755<br />
Con duc tor Tinned cop per<br />
In su la tion PVC<br />
CA BLE SIZES<br />
Sig nal cab le<br />
KLMA<br />
Num ber <strong>and</strong> di ame ter of<br />
the con duc tors mm 2 x 0,8+0,8 4 x 0,8+0,8<br />
EAN code (STTL code) 64 100+ 02 920 01-7 02 920 03-1<br />
Nomi nal di ame ters mm 4,5 5,0<br />
Mass kg/km 30 45<br />
De liv ery length m 500 500<br />
ELEC TRI CAL PROP ER TIES 20 °C<br />
Maxi mum con duc tor re sis tance Ω/km 36,7<br />
Mini mum in su la tion re sis tance MΩ x km 500<br />
Maxi mum volt age V 75<br />
KLMA is also available as halo gen free KLMA- HF ver sion.<br />
IDEN TI FI CA TION<br />
1. Conductor blue<br />
2. Conductor yel low<br />
3. Conductor white<br />
4. Conductor red<br />
SIG NAL CA BLES<br />
The ca ble fulfils the fire con di tion re quire ments of<br />
IEC 332-1.<br />
Unit Twisted con duc tors shielded with<br />
plas tic-alu min ium tape, earth con duc tor<br />
Sheath Grey LINYL- PVC<br />
The right to al tera tions re served.<br />
61