IN STRU MEN TA TION CA BLES<br />

56<br />

JA MAK ® & JA MAK ® ARM<br />

JOIN TING<br />

Pair shields <strong>and</strong> the com mon shield are spliced <strong>and</strong><br />

earthed by a cop per con duc tor. It is im por tant in the<br />

joint ing <strong>and</strong> ter mi nal con nec tions that the pair shields are<br />

in su lated one from<br />

the an other, ex cept <strong>for</strong> the com mon ground ing point.<br />

If the joint ing has to be EMC pro tected, the shields have to<br />

be jointed all around i.e. 360°.<br />

SPLIC ING<br />

1. The sheath is stripped. The in ner sheath is pulled<br />

open by the tear- off wire.<br />

2. The pair shield is opened <strong>and</strong> re moved<br />

1<br />

1<br />

1<br />

pull off<br />

1<br />

3. Splic ing of a pair<br />

pair sleeve<br />

2-12 pair<br />

25<br />

30<br />

50 40<br />

24 <strong>and</strong> 48 pairs<br />

2. cut<br />

1. cut<br />

earth conductor<br />

1<br />

2<br />

strip<br />

100<br />

1<br />

3<br />

1<br />

2<br />

1<br />

2<br />

1<br />

3 3<br />

2<br />

4 4<br />

3<br />

2<br />

4<br />

3<br />

4<br />

4<br />

1<br />

1<br />

1<br />

conductor sleeve<br />

joint gap<br />

1 1 1 1<br />

An in door ca ble is jointed with out steps 6 <strong>and</strong> 7.<br />

1<br />

1<br />

1 1<br />

The length of the splice de pends on the number of<br />

the pairs:<br />

Number of pairs 2 4 8 12 24 48<br />

Joint gap mm 280 280 280 280 400 400<br />

4. Splic ing of the earth con duc tor of the pair shield<br />

5. Com plete pair joint<br />

pair insulation<br />

Note! If the joint ing has to be EMC pro tected,<br />

the shields have to be jointed all around i.e. 360°.<br />

6. Splic ing of the in ner sheath<br />

7. Splic ing of the ar mour ing<br />

8. Com plete joint<br />

earth conductor splice<br />

1 1 1 1 1<br />

thermal protection earth conductor splice <strong>for</strong><br />

the common shield<br />

copper braid<br />

shrink-on tube<br />

soldering<br />

outer shrink-on tube inner shrink-on tube<br />

shrink-on tube<br />

The right to al tera tions re served.