1,5 mm 2<br />

AP PLI CA TION<br />

For fixed in stal la tion in a con duit, <strong>and</strong> <strong>for</strong> wir ing in<br />

ap pli ances, switch gear <strong>and</strong> con trol gear with<br />

a maxi mum volt age of 1000 V (a.c.) or a maxi mum of<br />

750 V (d.c.) to earth.<br />

Cur rent car ry ing ca paci ties ac cord ing to HD 384.5.523<br />

(or IEC 364- 5- 523): “Elec tri cal in stal la tion of build ings”<br />

-se ction 523: Cur rent car ry ing ca paci ties.<br />

Maxi mum per mis si ble tem pera ture of con duc tor:<br />

– in con tinu ous use +70 °C<br />

– in short cir cuit (max. 5 s) +160 °C<br />

Low est rec om mended han dling<br />

tem pera ture: -25 °C<br />

Mini mum rec om mended bend ing ra dius:<br />

– dur ing in stal la tion 8xD<br />

– in a fi nal in stal la tion if bent only once 3xD<br />

INSTALLATION CABLES<br />

Maxi mum per mis si ble ten sile stress<br />

dur ing in stal la tion: Ax50 N/mm²<br />

RATED VOLT AGE<br />

U o /U = 450/750 V<br />

STAN DARD<br />

SFS 5523 <strong>and</strong> CENE LEC HD 21<br />

Cross-section of conductor<br />

<strong>and</strong> colour mm² 1,5 VA 1,5 RU 1,5 MU 1,5 SI 1,5 KEVI<br />

EAN code (SSTL code) 64 100+<br />

coil 04 008 00-3 04 008 02-7 04 008 03-4 04 008 07-2 04 008 08-9<br />

Nominal overall diameter mm 2,7 2,7 2,7 2,7 2,7<br />

Total weight kg/km 20 20 20 20 20<br />

Direct current resistance of<br />

conductorat+20 °C max. Ω/km 12,1 12,1 12,1 12,1 12,1<br />

St<strong>and</strong>ard delivery length m 200 200 200 200 200<br />

2,5 mm 2<br />

CON STRUC TION<br />

Con duc tor An nealed cop per wire<br />

Cross-section of conductor <strong>and</strong><br />

colour mm² 2,5 VA 2,5 RU 2,5 MU 2,5 SI 2,5 KEVI<br />

EAN code (SSTL code) 64 100+<br />

coil 04 008 20-1 04 008 22-5 04 008 23-2 04 008 27-0 04 008 28-7<br />

Nominal overall diameter mm 3,3 3,3 3,3 3,3 3,3<br />

Total weight kg/km 31 31 31 31 31<br />

Direct current resistance of<br />

conductorat+20 °C max. Ω/km 7,41 7,41 7,41 7,41 7,41<br />

St<strong>and</strong>ard delivery length m 200 200 200 200 200<br />

Coil = shrink-wrapped coil<br />

Plas tic- in su la ted con duc tor<br />

ML H07V-U<br />

So lid con duc tor<br />

N<br />

Self- extinguishing IEC 332-1<br />

In su la tion Lead- free Li nyl PVC,<br />

core iden ti fi ca tion by col ours<br />