CON STRUC TION<br />

Con duc tor An nealed cop per:<br />

1,5 <strong>and</strong> 2,5 mm 2 solid<br />

6 <strong>and</strong> 10 mm 2 str<strong>and</strong>ed<br />

In su la tion Lead free PVC, core iden ti fi ca tion by<br />

col ours <strong>and</strong>/or num bers<br />

Fill ing Fill ing com pound<br />

WITH PROTECTIVE CONDUCTORS<br />

Number of conductors <strong>and</strong><br />

cross-section nxmm² 3 x 1,5 S 3 x 2,5 S<br />

EAN code (SSTL code) 64 100+ 04 130 51-3 04 130 52-0<br />

Nominal overall diameter mm 13 15<br />

Total weight kg/km 290 360<br />

Direct current resistance of<br />

conductor at +20 °C.max. Ω/km 12,1 7,41<br />

St<strong>and</strong>ard delivery length<br />

drum m 300/6C 300/7E<br />

WITH PROTECTIVE CONDUCTORS<br />

Number of conductors <strong>and</strong><br />

cross-section nxmm² 5 x 1,5 S 5 x 2,5 S<br />

EAN code (SSTL code) 64 100+ 04 130 57-5 04 130 58-2<br />

Nominal overall diameter mm 15 17<br />

Total weight kg/km 360 460<br />

Direct current resistance of<br />

conductor at +20 °C.max. Ω/km 12,1 7,41<br />

St<strong>and</strong>ard delivery length<br />

drum m 300/7E 300/8E<br />

WITHOUT PROTECTIVE CONDUCTORS<br />

Number of conductors <strong>and</strong><br />

cross-section nxmm² 7 x 1,5 7 x 2,5 12 x 1,5 19 x 1,5<br />

EAN code (SSTL code) 64 100+ 04 130 65-0 04 130 66-7 04 130 68-1 04 130 70-4<br />

Nominal overall diameter mm 16 18 20 23<br />

Total weight kg/km 430 560 610 820<br />

Direct current resistance of<br />

conductor at +20 °C.max. Ω/km 12,1 7,41 12,1 12,1<br />

St<strong>and</strong>ard delivery length<br />

drum m 400/8E 400/9E 400/11G 400/11G<br />

Electrical properties<br />

Capacitance between<br />

two adjacent conductors<br />

at +20 °C <strong>and</strong> 50 Hz nF/km<br />

Capacity to earth of<br />

one conductor<br />

at +20 °C <strong>and</strong> 50 Hz nF/km<br />

Ar mou red me tal- sheat hed cab le<br />

MJAMARM<br />

130...160<br />

210...280<br />

130...160<br />

220...290<br />

INSTALLATION CABLES<br />

Me tal lic screen AI- PE lami nate <strong>and</strong><br />

drain wire, 1,0 mm²<br />

Sheath White PE/lead free PVC<br />

Ar mour ing Two zinc- coated steel tapes<br />

Sheath Black lead free PVC<br />

- marked by me ters<br />

130...160<br />

210...280<br />

130...160<br />

210...280<br />