AP PLI CA TION<br />
For fixed in stal la tion in a con duit, <strong>and</strong> <strong>for</strong> wir ing in<br />
ap pli ances, switch gear <strong>and</strong> con trol gear with<br />
a maxi mum volt age of 1000 V (a.c.) or a maxi mum of<br />
750 V (d.c.) to earth.<br />
Maxi mum per mis si ble tem pera ture of con duc tor:<br />
- in con tinu ous use +90 °C<br />
- in a short cir cuit (max. 5 s) +160 °C<br />
Low est rec om mended<br />
han dling tem pera ture: -25 °C<br />
Mini mum rec om mended<br />
bend ing ra dius:<br />
- dur ing in stal la tion 8xD<br />
- in a fi nal in stal la tion if bent only once 3xD<br />
CON STRUC TION<br />
Con duc tor Tinned, an nealed cop per wires,<br />
str<strong>and</strong>ed flexi ble<br />
Plas tic- in su la ted jum per wire<br />
MKEMT 90 H07V2-K<br />
Tin ned, fle xib le con duc tor<br />
RATED VOLT AGE<br />
U o /U = 450/750 V<br />
STAN DARD<br />
SFS 5523 <strong>and</strong> CENE LEC HD 21<br />
Self- extinguishing IEC 332-1<br />
JUMPER WIRES<br />
In su la tion Lead-free Li nyl PVC, core iden ti fi ca tion<br />
by col ours<br />
Cross-section of conductors<br />
<strong>and</strong> colour mm² 1,5 MU 1,5 SI 1,5 KEVI 2,5 MU 2,5 SI 2,5 KEVI<br />
EAN code (SSTL code) 64 100+ 04 031 53-7 04 031 57-5 04 031 58-2 04 031 73-5 04 031 77-3 04 031 78-0<br />
Nominal overall diameter mm 3,1 3,1 3,1 3,7 3,7 3,7<br />
Total weight kg/km 21 21 21 32 32 32<br />
Direct current resistance of<br />
conductor at +20 °C max. Ω/km 13,7 13,7 13,7 8,21 8,21 8,21<br />
St<strong>and</strong>ard delivery length<br />
spool m 250 250 250 200 200 200<br />
35