CON TROL CA BLES<br />
30<br />
N<br />
AP PLI CA TION<br />
Ca ble <strong>for</strong> the con trol, meas ur ing <strong>and</strong> sig nal cir cuits<br />
of elec tri cal equip ment <strong>for</strong> fixed sur face <strong>and</strong><br />
flush- mounted in stal la tions, in doors <strong>and</strong> out doors.<br />
The con cen tric cop per con duc tor <strong>for</strong>ms a good<br />
elec tro me chani cal pro tec tion <strong>and</strong> a mod er ate<br />
pro tec tion against elec tri cal in ter fer ence.<br />
Maxi mum per mis si ble tem pera ture of con duc tor:<br />
- in con tinu ous use +70 °C<br />
- in a short cir cuit (max. 5 s) +160 °C<br />
Low est rec om mended han dling<br />
tem pera ture: -15 °C<br />
Mini mum rec om mended bend ing ra dius:<br />
- dur ing in stal la tion 10xD<br />
- in a fi nal in stal la tion if bent only once 8xD<br />
Maxi mum per mis si ble ten sile stress<br />
dur ing in stal la tion Ax50 N/mm²<br />
Elec tro mag netic com pati bil ity<br />
Plas tic- sheat hed cont rol cab le<br />
MCMO<br />
with con cent ric cop per con duc tor<br />
RATED VOLT AGE<br />
U o /U = 450/750 V<br />
STAN DARD<br />
SFS 3713<br />
Self- extinguishing IEC 332-1