30.01.2013 Views

Cables for Installations and Industry - Draka

Cables for Installations and Industry - Draka

Cables for Installations and Industry - Draka

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

IN STAL LA TION CA BLES<br />

8<br />

N<br />

AP PLI CA TION<br />

For per ma nent in stal la tion in a con duit, <strong>and</strong> <strong>for</strong> wir ing<br />

in ap pli ances, switch gear <strong>and</strong> con trol gear with<br />

a maxi mum volt age of 1000 V (a.c.) or a maxi mum of<br />

750 V (d.c.) to earth.<br />

Plas tic- in su la ted con duc tor<br />

MK 90 H07V2-R<br />

Stran ded con duc tor<br />

Cur rent car ry ing ca paci ties ac cord ing to HD 384.5.523<br />

(or IEC 364- 5- 523): “Elec tri cal in stal la tion of build ings”<br />

-se ction 523: Cur rent car ry ing ca paci ties.<br />

Maxi mum per mis si ble tem pera ture of con duc tor:<br />

- in con tinu ous use +90 °C<br />

- in a short cir cuit (max. 5 s) +160 °C<br />

Low est rec om mended han dling<br />

tem pera ture: -25 °C<br />

Mini mum rec om mended bend ing ra dius:<br />

- dur ing in stal la tion 8xD<br />

- in a fi nal in stal la tion if bent only once 3xD<br />

Maxi mum per mis si ble ten sile stress<br />

dur ing in stal la tion Ax50 N/mm²<br />

CON STRUC TION<br />

RATED VOLT AGE<br />

U o /U = 450/750 V<br />

STAN DARD<br />

SFS 5523 <strong>and</strong> CENE LEC HD 21<br />

Con duc tor An nealed cop per wires, str<strong>and</strong>ed In su la tion Lead-free Li nyl PVC, core iden ti fi ca tion<br />

by col ours<br />

1,5 mm2 2,5 mm2<br />

Cross-section of conductor <strong>and</strong><br />

colour mm² 1,5 RU 1,5 MU 1,5 SI 1,5 KEVI 2,5 RU 2,5 MU 2,5 SI 2,5 KEVI<br />

EAN code (SSTL code) 64 100+<br />

coil 04 017 04-3 04 017 03-6 04 017 05-0 04 017 02-9 04 017 08-1 04 017 07-4 04 017 09-8 04 017 06-7<br />

Nominal overall diameter mm 3,0 3,0 3,0 3,0 3,7 3,7 3,7 3,7<br />

Total weight kg/km 22 22 22 22 35 35 35 35<br />

Direct current resistance of<br />

conductorat+20 °C max. Ω/km 12,1 12,1 12,1 12,1 7,41 7,41 7,41 7,41<br />

St<strong>and</strong>ard delivery length m 250 250 250 250 200 200 200 200<br />

Coil = shrink-wrapped coil<br />

Self- extinguishing IEC 332-1