N<br />

AP PLI CA TION<br />

For fixed in stal la tion mainly as a con nect ing ca ble <strong>for</strong><br />

post mounted lu mi naires.<br />

Maxi mum per mis si ble tem pera ture of con duc tor:<br />

- in con tinu ous use +70 °C<br />

- in a short cir cuit (max. 5 s) +160 °C<br />

Low est rec om mended<br />

han dling tem pera ture: -25 °C<br />

Mini mum rec om mended bend ing ra dius:<br />

- dur ing ca ble pull ing 10xD<br />

- in a fi nal in stal la tion if bent only once 3xD<br />

Maxi mum per mis si ble ten sile stress: Ax50 N/mm²<br />

CON STRUC TION<br />

Con duc tor An nealed cop per wires,<br />

str<strong>and</strong>ed flexi ble<br />

In su la tion PVC<br />

Cab le <strong>for</strong> lamp- posts<br />

MKEMP<br />

Fle xib le con duc tor<br />

RATED VOLT AGE<br />

U o /U = 450/750 V<br />

STAN DARDI<br />

SFS 5523 <strong>and</strong> SFS 2091<br />

Self- extinguishing IEC 332-1<br />

Sheath PVC<br />

INSTALLATION CABLES<br />

Cross-section of conductors<br />

<strong>and</strong> colour mm² 2,5 MU 2,5 SI 2,5 KEVI<br />

EAN code (SSTL code) 64 100+ 04 034 03-3 04 034 07-1 04 034 08-8<br />

Nominal overall diameter mm 8,0 8,0 8,0<br />

Total weight kg/km 82 82 82<br />

Direct current resistance of<br />

conductor at +20 °C max. Ω/km 7,98 7,98 7,98<br />

St<strong>and</strong>ard delivery length<br />

coil m 100 100 100<br />