18<br />

Setting the flushing interval (SW2) (SU11/DU11 only)<br />

The flushing interval is the period between two flushing cycles. A timer built<br />

into the controller logs the time (based on the hours of operation of the<br />

atomizer). A flushing cycle is initiated each time the specified interval has<br />

elapsed.<br />

The time between two flushing cycles can be defined as 30, 60, 120 or 240<br />

minutes. The time to be set depends on the prevailing operating conditions<br />

(dustiness, water quality).<br />

Recommendation: – Very dusty conditions <strong>and</strong>/or hard water:<br />

Flushing interval 30 minutes<br />

– Normal dustiness <strong>and</strong>/or medium-hardness water:<br />

Flushing interval 60 - 120 minutes<br />

– Slight dustiness <strong>and</strong>/or demineralized water:<br />

Flushing interval 120 - 240 minutes<br />

Setting of switch SW2 Flushing interval in minutes<br />

1 30<br />

2 60<br />

3 120<br />

4 240<br />

Selection of the supply voltage (SW3)<br />

The <strong>ABS2</strong> supports two different voltage ranges. Selection of the appropriate<br />

supply voltage is done via switch SW3.<br />

Setting of switch SW3 Supply voltage<br />

115 100…115 VAC/50…60 Hz<br />

230 220…240 VAC/50…60 Hz<br />

To conclude setup work connect the grounding wire to the cover, then fix<br />

the cover with the 4 Phillips screws.