8. Appliance specifications<br />

8.1 Technical data<br />

Appliance configuration<br />

Designation AU35+SU11/21 AU90+SU11/21 AU35+DU11/21 AU90+DU11/21<br />

Humidification capacity 3.5 l/h 9 l/h 7 l/h 18 l/h<br />

Air circulation 300 m3 /h 800 m3 /h 600 m3 /h 1600 m3 /h<br />

Power consumption 200 W 290 W 400 W 580 W<br />

Supply voltage 100…115VAC/50…60Hz or 220…240VAC / 50…60Hz<br />

Atomizer fuse F1 100…115V= 16A, slow-blow/250V or 220…240V= 6.3A, slow-blow/250V<br />

Primary fuse F2 100…115V= 630mA, slow-blow/250V or 220…240V= 315mA, slow-blow/250V<br />

Secondary fuse F3 1.6 A, slow-blow/250V<br />

Dimensions in mm (W x H x D) 462 x 474 x 511 462 x 704 x 511 1000 x 474 x 511 1000 x 704 x 511<br />

Weight (dry) 25.4 kg 27.5 kg 45.8 kg 50 kg<br />

Water content<br />

Water consumption<br />

1 l 1 l 2 l 2 l<br />

– without drain max. 3.5 l/hr max. 9.0 l/hr max. 7.0 l/hr max. 18.0 l/hr<br />

– Flushing cycle 30 min. max. 7.5 l/h max. 13.0 l/h max. 15.0 l/hr max. 26.0 l/hr<br />

– Flushing cycle 60 min. max. 5.5 l/hr max. 11.0 l/hr max. 11.0 l/hr max. 22.0 l/hr<br />

– Flushing cycle 120 min. max. 4.5 l/hr max. 10.0 l/hr max. 9.0 l/hr max. 20.0 l/hr<br />

– Flushing cycle 240 min. max. 4.0 l/hr max. 9.5 l/hr max. 8.0 l/hr max. 19.0 l/hr<br />

Feed-water pressure 100 - 600 kPa (1.0 - 6.0 bar)<br />

Pressurized water connection 8 mm OD/6 mm ID tubing, connection 3/4" or 1/2" (outside thread)<br />

Water drain connection Inner Ø 40 mm<br />

Drive Maintenance-free electric motor with thermostatic switch<br />

Control External humidistat (e.g. <strong>Defensor</strong> H5)<br />

Test <strong>and</strong> conformity certificates SEV, CE<br />

8.2 <strong>Operating</strong> conditions<br />

Temperature range: 2 - 40 °C<br />

Note: Contact your <strong>Defensor</strong> dealer if lower temperatures<br />

are involved.<br />

Humidity range: 0 - 98 % rh<br />

Water quality: Tap water<br />

Water demineralization is recommended if the mineral<br />

salt content of the water is high (>15 dH°, >27 fH°).<br />

Air: If the air is very dirty, it is advisable to use the pocketfilter<br />

unit FU2 in the primary air system <strong>and</strong> the ringfilter<br />

FU3 (AU90 only) in the secondary air system.<br />

Note: See section 4.1 “Appliance location” for additional information.<br />