3. Principle of operation<br />

1<br />

The <strong>ABS2</strong> adiabatic humidification system operates according to the atomization<br />

principle.<br />

The water is drawn in through suction tube (1) from the reservoir <strong>and</strong> is<br />

hurled from impeller (2) <strong>and</strong> spinning disk (3) against atomizer grid (4),<br />

thereby producing an aerosol (fog).<br />

Impeller (2) draws in room air through the bottom of the base unit. This air<br />

then passes through a filter (FU1 or FU2) <strong>and</strong> forms the primary stream<br />

which transports the aerosol to the atomizer outlet.<br />

Fan (6) draws in ambient air through the top surface of the AU35 atomizer<br />

unit (or through the annular inlet of the AU90) <strong>and</strong> is also routed to the<br />

outlet. This secondary air stream takes up the aerosol <strong>and</strong> discharges it into<br />

the room. The separate air-guidance systems result in the uniform spatial<br />

distribution of the aerosol.<br />

2<br />

6<br />

FU1/FU2<br />

5<br />

3<br />

4<br />

The atomizer unit is powered by a maintenance-free electric motor (5)<br />

which is controlled by an external humidistat <strong>and</strong> the built-in controller.<br />

In both basic configurations of the base units, the water supply to the<br />

reservoir is controlled by the float switch <strong>and</strong> the inlet valve (SU11/DU11)<br />

or the two inlet valves (SU21/DU21), respectively.<br />