7.2 Fault elimination<br />

28<br />

Notes regarding fault elimination<br />

– Before eliminating faults, the <strong>Defensor</strong> <strong>ABS2</strong> must be taken out of<br />

operation according chapter 5.2.<br />

Danger! Make sure the mains supply to the humidifier is disconnected<br />

(check with voltage tester) <strong>and</strong> the stop cock of the water supply is<br />

closed.<br />

– Have faults eliminated by adequately qualified <strong>and</strong> trained personnel<br />

only (e.g. by a service engineer of your <strong>Defensor</strong> supplier).<br />

Malfunctions caused by the electrical installation must be repaired by<br />

authorized personnel only.<br />

Replacement of the fuses<br />

Caution! The electronic components on the control PCB are very susceptible<br />

to electrostatic discharge. When carrying out repairs to the control unit,<br />

appropriate measures (ESD-protection) must be taken to prevent damage<br />

to electronic components.<br />

Danger, lethal voltage! Before replacing defective fuses, set the<br />

<strong>Defensor</strong> <strong>ABS2</strong> out of operation <strong>and</strong> disconnect the unit from the<br />

mains according to chapter 5.2.<br />

• Loosen the 4 screws of the cover on the left side of the base unit.<br />

Carefully lift off the cover, then remove the grounding wire from the<br />

cover.<br />

F2<br />

F1<br />

F3<br />

• Replace fuses F1, F2 <strong>and</strong> F3 of the control PCB only with fuses<br />

matching the specifications below:<br />

– Atomizer fuse F1:<br />

Supply voltage 220…240V: 6.3 A, slow-blow/nom. voltage 250V<br />

Supply voltage 100…115V: 16 A, slow-blow/nom. voltage 250V<br />

– Primary fuse F2:<br />

Supply voltage 220…240V: 315 mA, slow-blow/nom. voltage 250V<br />

Supply voltage 100…115V: 630 mA, slow-blow/nom. voltage 250V<br />

– Secondary fuse F3: 1.6 A, slow-blow/nom. voltage 250V<br />

Caution! Never use refurbished fuses. Do not bridge the fuse holder.<br />

• Following replacement of the fuse(s) connect the grounding wire to the<br />

cover, then fasten the cover with the 4 Phillips screws.