5. Commissioning, operation <strong>and</strong> shutdown<br />
5.1 Commissioning/operation<br />
5.2 Shutdown<br />
Proceed as follows to ready the humidifier for operation:<br />
It is assumed that the unit has already been installed, connected <strong>and</strong><br />
configured according to the instructions (see chapter 4).<br />
• Turn on the water supply.<br />
Attention! Appliances with base unit SU21 or DU21; check whether the<br />
drain neck is closed properly.<br />
• On the external humidistat set the reference humidity to the desired<br />
value.<br />
• Actuate the maintenance switch.<br />
Appliances with base unit SU11 or DU11: the water reservoir is flushed<br />
<strong>and</strong> then filled up to the working level.<br />
Appliances with base unit SU21 or DU21: the water reservoir is filled up<br />
to the working level.<br />
The humidifier is now in the ready mode. The atomizer will be activated only<br />
if the air humidity is lower than the set reference value. On base units SU11/<br />
DU11 the flushing of the water reservoir always takes place according to<br />
the preset flushing interval, even in st<strong>and</strong>by mode (see section “Setting the<br />
flushing interval” in chapter 4.5).<br />
If malfunction occurs during operation, the red error indicator on the<br />
front panel of the base unit starts flashing or lights up constantly (for<br />
additional information refer to chapter 7).<br />
Proceed as follows to put the humidifier out of operation:<br />
• Disconnect the humidifier from the mains (set the maintenance<br />
switch to off) <strong>and</strong> secure the system against unintentional start-up.<br />
Danger, lethal voltage! If the humidistat controlling your unit is fed<br />
by an external power supply, the external voltage is applied to<br />
the control PCB. In this case you must disconnect the humidistat<br />
from power supply.<br />
The water reservoir of appliances equipped with base unit SU11 or<br />
DU11 is drained <strong>and</strong> flushed automatically at shutdown time.<br />
The water reservoir of appliances with base unit SU21 or DU21 should<br />
be drained manually via the drain neck if the humidifier is to be set out<br />
of operation for an extended period (hygiene).<br />
• Turn off water supply (close sieving filter valve).<br />
19