Why provide diffusers?<br />
<strong>Axial</strong>-flow fans generate a total pressure<br />
increase (�pt) which comprises<br />
a static pressure portion (ps) and a<br />
dynamic one (pd). The impeller of an<br />
axial-flow fan consists of blades and<br />
hub located in the airflow. The result<br />
is a circular flow of considerable velocity.<br />
This high flow velocity (c) gives<br />
rise to a high dynamic pressure.<br />
When an axial-flow fan is allowed to<br />
discharge freely into a room, as is<br />
often the case, the entire dynamic<br />
Diffuser for AXO series fans<br />
Sizes:<br />
315/400/560/630/800/1000-1250<br />
ØD<br />
Øk<br />
Øi.d.<br />
z x d<br />
L<br />
�<br />
Øi.d. 1<br />
ØD 1<br />
AXIAL FLOW FANS AXN SERIES<br />
AXO + AXN SERIES<br />
MAIN DIFFUSER DIMENSIONS<br />
pressure (related to the annular<br />
cross section) ceases to be effective<br />
and must be considered a loss. A diffuser<br />
will reduce the outlet velocity<br />
substantially and thereby prevent<br />
much of this dynamic pressure loss.<br />
In other words, to achieve an otherwise<br />
identical static pressure difference,<br />
the total pressure increase to<br />
be generated can be reduced, and<br />
so can be the output of the fan motor.<br />
Another benefit lies in the increased<br />
outlet surface area, which results in a<br />
Diffuser for AXN series fans<br />
Sizes: 315 bis 1250<br />
ØD<br />
Øi.d.<br />
Øk<br />
z x d<br />
L<br />
Øi.d. 2<br />
ØD2 ØD<br />
Øk<br />
Diffuser for AXN series fans<br />
with interior core<br />
Sizes: 315 bis 1250<br />
Size Ø i.d. Ø i.d. 1 Ø i.d. 2 Ø d3 Ø D Ø D1 Ø D2 Ø D3 Ø k Ø k1 L L1z x d z x d1 315 322 404 360 - 386 424 380 - 356 - 160 - 8 x 9,5 -<br />
355 360 - 404 - 425 - 424 - 395 - 180 - 8 x 9,5 -<br />
400 404 507 451 - 468 527 471 - 438 - 200 _ 12 x 9,5 -<br />
450 451 567 507 - 517 - 527 - 487 - 225 - 12 x 9,5 -<br />
500 507 637 567 282 571 657 587 712 541 674 250 600 12 x 9,5 16 x 11,5<br />
560 567 712 637 315 643 - 657 789 605 751 280 670 16 x 11,5 16 x 11,5<br />
630 637 800 712 355 712 820 732 875 674 837 315 750 16 x 11,5 24 x 11,5<br />
710 712 894 800 397 789 - 820 972 751 934 355 850 16 x 11,5 24 x 11,5<br />
800 800 1006 894 446 875 1026 914 1081 837 1043 400 950 24 x 11,5 24 x 11,5<br />
900 894 1128 1006 502 972 - 1026 1254 934 1174 450 1060 24 x 11,5 24 x 11,5<br />
1000 1006 1264 1128 562 1081 1284 1148 1391 1043 1311 500 1200 24 x 11,5 24 x 11,5<br />
1120 1128 1418 1264 630 1214 1438 1284 1545 1174 1465 560 1340 24 x 11,5 24 x 11,5<br />
1250 1264 1589 1416 710 1351 1609 1436 1717 1311 1637 630 1510 24 x 11,5 32 x 11,5<br />
Diffuser dimensions for sizes 1400 through to 2500 are available upon request.<br />
� A flat flange must be provided for duct connection. Dimensions in mm. Dimensional and design changes reserved.<br />
�<br />
Øi.d.<br />
z x d<br />
Ød 3<br />
L 1<br />
014<br />
more uniform application of the airflow<br />
to downstream components.<br />
For <strong>TLT</strong> diffusers with interior core<br />
for use with AXN series axial-flow<br />
fans and for diffusers without interior<br />
core for AXN or AXO series fans,<br />
please enquire with our headquarter<br />
or field staff. These products will be<br />
rated using special computer software.<br />
Øi.d. 1<br />
z x d 1<br />
Øk1 ØD3