Rating sheet for a volume flow<br />
measuring system<br />
Example given for an AXN<br />
12/56/1000 axial-flow fan<br />
Differential pressure [Pa]<br />
900<br />
800<br />
700<br />
600<br />
500<br />
400<br />
300<br />
200<br />
100<br />
Density 1,2 kg/m 3<br />
Density 1,1 kg/m 3<br />
Density 1,0 kg/m 3<br />
Density 0,9 kg/m 3<br />
Density 1,3 kg/m 3<br />
VOLUME FLOW MEASURING SYSTEM VME<br />
FOR AXIAL-FLOW FANS<br />
Nominal size NG 1000<br />
Rotational speed n 1500 rpm<br />
Tip speed u2 79 m/s<br />
Density 1,2 kg/m3 Dynamic viscosity � 1,80E-05 Pa s<br />
Reference cross-section A ring 0,5391 m 2<br />
Reference diameter Dh ref 0,8285 m<br />
Rated fan total pressure increase dpt 500 Pa<br />
Rated volume flow VA 45000 m3/h Rated flow within measuring range* VA > 32100 m3/h Correction factor at VA k 2,13<br />
Differential pressure under rating conditions dp 71 Pa<br />
* At smaller volume flows the differential pressure values are of insufficient magnitude.<br />
The accuracy of the volume flow measuring system depends on the pressure gauge employed as well as on the flow approach situation. Under unperturbed<br />
incoming flow condition and taking into account the inlet density, the tolerance is approx. 5% of the actual volume flow value.<br />
Input data Calculated data Operating limits<br />
�<br />
0<br />
0 20000 40 000 60 000 80 000 100 000 120 000<br />
Volume flow [m 3 /h]<br />