27.02.2013 Views

Axial innen engl - TLT Turbo GmbH

Axial innen engl - TLT Turbo GmbH

Axial innen engl - TLT Turbo GmbH

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Am Weinberg 68 · D-36251 Bad Hersfeld/Germany<br />

Phone: +49.6621.950-0 · Fax: +49.6621.950-100<br />

Rating sheet for a volume flow<br />

measuring system<br />

Example given for an AXN<br />

12/56/1000 axial-flow fan<br />

Differential pressure [Pa]<br />

900<br />

800<br />

700<br />

600<br />

500<br />

400<br />

300<br />

200<br />

100<br />

Density 1,2 kg/m 3<br />

Density 1,1 kg/m 3<br />

Density 1,0 kg/m 3<br />

Density 0,9 kg/m 3<br />

Density 1,3 kg/m 3<br />

VOLUME FLOW MEASURING SYSTEM VME<br />

FOR AXIAL-FLOW FANS<br />

Nominal size NG 1000<br />

Rotational speed n 1500 rpm<br />

Tip speed u2 79 m/s<br />

Density 1,2 kg/m3 Dynamic viscosity � 1,80E-05 Pa s<br />

Reference cross-section A ring 0,5391 m 2<br />

Reference diameter Dh ref 0,8285 m<br />

Rated fan total pressure increase dpt 500 Pa<br />

Rated volume flow VA 45000 m3/h Rated flow within measuring range* VA > 32100 m3/h Correction factor at VA k 2,13<br />

Differential pressure under rating conditions dp 71 Pa<br />

* At smaller volume flows the differential pressure values are of insufficient magnitude.<br />

The accuracy of the volume flow measuring system depends on the pressure gauge employed as well as on the flow approach situation. Under unperturbed<br />

incoming flow condition and taking into account the inlet density, the tolerance is approx. 5% of the actual volume flow value.<br />

Input data Calculated data Operating limits<br />

�<br />

0<br />

0 20000 40 000 60 000 80 000 100 000 120 000<br />

Volume flow [m 3 /h]<br />

024

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!