RT-PRC006-EN<br />

General<br />

Data<br />

(7½ - 10 Tons)<br />

High Efficiency<br />

Table GD-7 — General Data<br />

7½ Ton Convertible 8½ Ton Convertible 10 Ton Convertible<br />

YHC092A3, A4, AW YHC102A3, A4, AW YHC120A3, A4, AW<br />

Cooling Performance1 Gross Cooling Capacity 94,000 103,000 117,000<br />

EER2 11.5 8 11.5 9 11.2 10<br />

Nominal CFM / ARI Rated CFM 3,000/2,625 3,400/3,000 4,000/3,200<br />

ARI Net Cooling Capacity 90,0008 98,0009 109,00010 Integrated Part Load Value3 11.8 8 11.8 9 11.7 10<br />

System Power (KW) 7.83 8 8.529 9.7310 Heating Performance4 Heating Models Low Medium High Low Medium High Low Medium High<br />

Heating Input (Btu) 120,000 150,000 200,000 120,000 150,000 200,000 150,000 200,000 250,000<br />

Heating Output (Btu) 97,200 121,500 162000 97,200 121,500 162000 121,500 162,000 202,500<br />

AFUE% 5 81 81 81 81 81 81 81 81 81<br />

Steady State Efficiency (%) 81 81 80 81 81 80 81 81 81<br />

No. Burners 3 3 4 3 3 4 3 4 5<br />

No. Stages<br />

<strong>Gas</strong> Supply Line Pressure<br />

1 2 2 1 2 2 2 2 2<br />

Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0<br />

LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0<br />

<strong>Gas</strong> Connection Pipe Size (in.) 1/2 3/4 3/4 1/2 3/4 3/4 3/4 3/4 3/4<br />

Compressor<br />

No./Type 2/Scrolls 2/Scrolls 2/Scrolls<br />

Outdoor Sound Rating (dB) 6 91 89 88<br />

Outdoor Coil - Type Lanced Lanced Lanced<br />

Tube Size (in.) OD 0.3125 0.3125 0.3125<br />

Face Area (sq ft) 17.5 19.83 27.21<br />

Rows/FPI 3/17 3/17 3/17<br />

Indoor Coil - Type Lanced Lanced Lanced<br />

Tube Size (in.) 0.3125 0.3125 0.3125<br />

Face Area (sq ft) 12.36 12.36 12.36<br />

Rows/FPI 3/16 4/16 5/16<br />

Refrigerant Control Short Orifice Short Orifice Short Orifice<br />

Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT<br />

Outdoor Fan - Type Propeller Propeller Propeller<br />

No. Used/Diameter (in.) 1/26 1/26 1/26<br />

Drive Type/No. Speeds Direct/1 Direct/1 Direct/1<br />

CFM 6200 6600 7000<br />

No. Motors/HP 1/0.70 1/0.75 1/0.75<br />

Motor RPM 1075 1,075 1,075<br />

Belt Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal<br />

No. Used/Diameter (in.) 1/15 x 15 1/15 x 15 1/15 x 15<br />

Drive Type/No. Speeds Belt/Variable Sheave Belt/Variable Sheave Belt/Variable Sheave<br />

No. Motors 1 1 1<br />

Motor HP (Standard/Oversized) 2.00/3.00 2.00/3.00 3.00/5.00<br />

Motor RPM (Standard/Oversized) 1,750/1,750 1,750/1,750 1,750/3,450<br />

Motor Frame Size (Standard/Oversized) 56/56 56/56 56/56<br />

Filters - Type Furnished 11 Throwaway Throwaway Throwaway<br />

(No.) Size Recommended (4) 20 x 25 x 2 (4) 20 x 25 x 2 (4) 20 x 25 x 2<br />

Optional Reheat Coil - Type<br />

Tube Size (in.) OD<br />

Lanced<br />

0.375<br />

Lanced<br />

0.375<br />

Lanced<br />

0.375<br />

Face Area (sq. ft.) 5.19 5.19 5.19<br />

Rows/FPI 2/16 2/16 2/16<br />

Refrigerant Charge (Lbs of R-22) 7 Notes:<br />

6.4 Circuit 1/6.2 Circuit 2 7.4 Circuit 1/7.1 Circuit 2 11.0 Circuit 1/7.3 Circuit 2<br />

1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect<br />

of fan motor heat. <strong>Units</strong> are suitable for operation to ±20% of nominal cfm. <strong>Units</strong> are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on<br />

ARI Standard 210/240.<br />

2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.<br />

3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. <strong>Units</strong> are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.<br />

4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for<br />

elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.<br />

5. AFUE is rated in accordance with DOE test procedures.<br />

6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.<br />

7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.<br />

8. YHC092A when applied in a horizontal configuration has an 11.3 EER, 89,000 ARI Net Cooling Capacity, 11.4 Integrated Part Load Value, and 7.88 System Power (KW).<br />

9. YHC102A when applied in horizontal configuration has an 11.3 EER, 11.3 IPLV, 97,000 ARI Net Cooling Capacity and 8.58 System Power (KW).<br />

10. YHC120A when applied in a horizontal configuration has an 10.7 EER, 11.2 IPL, 108,000 ARI Net Cooling and 10.09 System Power (KW).<br />

11. Optional 2” pleated filters also available.<br />

27