RT-PRC006-EN<br />

Performance<br />

Data<br />

(4 Ton)<br />

High Efficiency<br />

Table PD-62— Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor &<br />

Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive<br />

1280 681 0.26 755 0.32 816 0.38 870 0.45 921 0.51 968 0.58 1013 0.65 1053 0.72 1091 0.79 1127 0.86<br />

1440 748 0.36 817 0.43 876 0.49 927 0.56 976 0.63 1022 0.70 1065 0.78 1106 0.85 1144 0.93 1180 1.01<br />

1600 816 0.47 879 0.55 937 0.62 987 0.70 1033 0.78 1076 0.85 1119 0.93 1158 1.01 1197 1.10 1233 1.18<br />

1760 885 0.61 943 0.69 999 0.78 1049 0.86 1093 0.94 1135 1.03 1174 1.11 1213 1.20 1250 1.29 1286 1.38<br />

1920 956 0.77 1009 0.86 1062 0.96 1110 1.05 1154 1.14 1195 1.23 1232 1.32 1269 1.41 1304 1.50 — —<br />

Table PD-62 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard<br />

Motor & Drive<br />

1280 1162 0.94 1193 1.01 1225 1.09 1255 1.16 1284 1.23<br />

1440 1214 1.09 1247 1.18 1278 1.26 1309 1.35 1337 1.43<br />

1600 1268 1.27 1300 1.35 1332 1.45 — — — —<br />

1760 1320 1.47 — — — — — — — —<br />

1920 — — — — — — — — — —<br />

1-HP Standard Motor & Field Supplied High Static Drive (2)<br />

Table PD-63 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard<br />

Motor & Drive<br />

1280 1169 0.96 1201 1.03 1231 1.10 1262 1.17 1290 1.24<br />

1440 1222 1.11 1256 1.20 1286 1.28 1317 1.37 1346 1.45<br />

1600 1278 1.29 1311 1.38 1342 1.48 — — — —<br />

1760 — — — — — — — — — —<br />

1920 — — — — — — — — —<br />

1-HP Standard Motor & Field Supplied High Static Drive (2)<br />

1-HP Standard Motor & Field Supplied High Static Drive (2)<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other<br />

options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.<br />

2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our<br />

tabular data will not result in nuisance tripping or premature motor failure. Our<br />

product’s warranty will not be affected.<br />

Table PD-63 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor &<br />

Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive<br />

1280 698 0.28 769 0.34 828 0.40 881 0.46 932 0.52 978 0.59 1021 0.66 1061 0.73 1099 0.81 1134 0.88<br />

1440 767 0.37 834 0.44 890 0.51 941 0.58 988 0.65 1034 0.72 1077 0.80 1116 0.87 1153 0.95 1190 1.03<br />

1600 837 0.50 899 0.57 955 0.65 1003 0.72 1048 0.80 1091 0.88 1132 0.96 1171 1.04 1209 1.12 1245 1.21<br />

1760 908 0.64 966 0.73 1020 0.81 1067 0.89 1110 0.98 1151 1.06 1190 1.15 1228 1.23 1264 1.32 1300 1.41<br />

1920 981 0.82 1035 0.91 1085 1.00 1133 1.09 1174 1.18 1213 1.27 1250 1.37 1286 1.46 — — — —<br />

1-HP Standard Motor & Field Supplied High Static Drive (2)<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other<br />

options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.<br />

2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our<br />

tabular data will not result in nuisance tripping or premature motor failure. Our<br />

product’s warranty will not be affected.<br />

61