RT-PRC006-EN<br />

Performance<br />

Data<br />

(8½ Ton)<br />

Standard Efficiency<br />

Table PD-48 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2720 607 0.59 655 0.69 697 0.80 744 0.93 791 1.07 834 1.21 871 1.34 904 1.46 933 1.58 962 1.70<br />

3060 672 0.81 715 0.92 755 1.04 792 1.16 834 1.31 876 1.47 917 1.63 953 1.78 985 1.93 1013 2.06<br />

3400 739 1.09 776 1.20 814 1.34 849 1.47 882 1.61 920 1.77 958 1.94 996 2.12 1030 2.29 1063 2.47<br />

3740 807 1.43 839 1.54 875 1.69 907 1.83 938 1.98 969 2.13 1003 2.30 1037 2.49 1072 2.69 1106 2.88<br />

4080 875 1.83 903 1.95 935 2.10 968 2.26 997 2.42 1025 2.58 1053 2.74 1084 2.93 1116 3.13 1148 3.34<br />

3-HP Oversized Motor & Drive<br />

Table PD-48 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

2720 988 1.81 1013 1.93 1037 2.05 1061 2.17 1084 2.28 1106 2.40 1128 2.52 1150 2.64 1172 2.76 1192 2.88<br />

3060 1040 2.19 1065 2.33 1090 2.46 1113 2.59 1136 2.72 1158 2.86 1179 2.99 1199 3.12 1220 3.25 1239 3.38<br />

3400 1091 2.62 1117 2.78 1141 2.92 1165 3.07 1188 3.22 1210 3.37 — — — — — — — —<br />

3740 1137 3.07 1166 3.27 1193 3.44 — — — — — — — — — — — — — —<br />

4080 — — — — — — — — — — — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-49 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *H— High Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2720 625 0.63 671 0.73 713 0.84 762 0.98 807 1.12 849 1.26 883 1.38 915 1.50 944 1.62 971 1.74<br />

3060 692 0.86 734 0.98 772 1.10 811 1.23 854 1.38 896 1.54 934 1.70 969 1.85 997 1.99 1026 2.12<br />

3400 760 1.15 799 1.28 834 1.41 868 1.55 903 1.70 942 1.87 980 2.04 1016 2.22 1049 2.39 1079 2.56<br />

3740 828 1.50 863 1.64 898 1.79 929 1.94 960 2.08 993 2.25 1027 2.44 1062 2.63 1096 2.82 1127 3.02<br />

4080 898 1.92 929 2.07 962 2.23 992 2.39 1020 2.55 1048 2.71 1078 2.89 1110 3.09 1142 3.30 — —<br />

3-HP Oversized Motor & Drive<br />

Table PD-49 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

2720 998 1.86 1022 1.97 1046 2.09 1069 2.21 1092 2.33 1115 2.45 1136 2.56 1158 2.69 1179 2.80 1200 2.93<br />

3060 1052 2.26 1077 2.39 1101 2.52 1124 2.66 1146 2.79 1167 2.92 1188 3.05 1209 3.18 1229 3.31 1249 3.45<br />

3400 1106 2.71 1131 2.86 1155 3.01 1179 3.16 1202 3.31 1222 3.45 — — — — — — — —<br />

3740 1157 3.21 1185 3.39 — — — — — — — — — — — — — — — —<br />

4080 — — — — — — — — — — — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />