64<br />

Performance<br />

Data<br />

(6 Ton)<br />

High Efficiency<br />

Table PD-68— Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1920 — — — — 597 0.37 652 0.44 700 0.51 745 0.58 788 0.66 829 0.74 869 0.82 906 0.91<br />

2160 — — 575 0.38 629 0.46 683 0.54 730 0.62 774 0.70 815 0.78 854 0.86 893 0.95 929 1.04<br />

2400 561 0.41 615 0.49 664 0.57 714 0.65 762 0.74 805 0.83 844 0.92 882 1.01 918 1.10 954 1.20<br />

2640 606 0.53 657 0.62 703 0.70 747 0.79 792 0.88 835 0.98 875 1.08 912 1.18 947 1.27 980 1.37<br />

2880 651 0.67 699 0.77 743 0.85 785 0.94 825 1.05 867 1.15 906 1.26 943 1.37 978 1.47 1010 1.58<br />

Table PD-68 — Continued<br />

2-HP Oversized Motor & Drive<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit<br />

(or 2 HP Oversized Motor & Drive)<br />

1920 941 0.99 977 1.07 1009 1.15 1041 1.23 1073 1.32 1103 1.40 1132 1.49 1159 1.57 1187 1.66 1213 1.75<br />

2160 964 1.13 997 1.23 1031 1.32 1061 1.41 1093 1.50 1123 1.60 1151 1.69 1179 1.78 1207 1.87 1234 1.97<br />

2400 988 1.29 1020 1.39 1054 1.50 1085 1.60 1114 1.70 1143 1.80 1171 1.90 1200 2.01 1227 2.11 1254 2.21<br />

2640 1014 1.47 1046 1.58 1077 1.69 1107 1.80 1138 1.91 1166 2.02 1193 2.13 1222 2.25 — — — —<br />

2880 1042 1.68 1073 1.79 1103 1.90 1132 2.02 1162 2.14 1190 2.26 — — — — — — — —<br />

2-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000<br />

1. Field Supplied Fan Sheave AK84 and Belt AX34 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-69 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*H — High Heat — Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1920 — — 574 0.34 631 0.41 681 0.48 727 0.55 771 0.63 814 0.71 853 0.79 892 0.87 928 0.95<br />

2160 562 0.36 616 0.44 671 0.52 719 0.60 763 0.68 805 0.76 845 0.84 884 0.93 921 1.02 957 1.11<br />

2400 612 0.48 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29<br />

2640 663 0.63 709 0.71 754 0.80 798 0.90 842 1.00 881 1.10 917 1.19 951 1.29 986 1.39 1018 1.49<br />

2880 715 0.80 758 0.88 799 0.98 840 1.08 880 1.19 920 1.30 955 1.41 990 1.51 1022 1.62 1053 1.72<br />

2-HP Oversized<br />

Motor & Drive<br />

Table PD-69 — Continued<br />

1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard 1-HP Standard Motor & High Static Drive Kit<br />

Motor & Drive (or 2 HP Oversized Motor & Drive)<br />

1920 963 1.04 997 1.12 1028 1.20 1061 1.28 1090 1.36 1119 1.45 1149 1.54 1177 1.63 1203 1.71 1229 1.80<br />

2160 990 1.21 1023 1.30 1055 1.39 1086 1.48 1115 1.57 1144 1.66 1173 1.76 1200 1.85 1227 1.95 1253 2.04<br />

2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 — —<br />

2640 1050 1.59 1081 1.70 1111 1.81 1141 1.93 1170 2.04 1198 2.15 1226 2.27 — — — — — —<br />

2880 1084 1.83 1114 1.94 1143 2.06 1172 2.18 1199 2.30 — — — — — — — — — —<br />

2-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000<br />

1. Field Supplied Fan Sheave AK84 and Belt AX34 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />