RT-PRC006-EN<br />
Performance<br />
Data<br />
(10 Ton)<br />
Standard Efficiency<br />
Table PD-52 — Belt Drive Evaporator Fan Performance — 10 Ton — YSC120A3,A4,AW, AK *L,M — Low and Medium Heat — Horizontal Airflow<br />
External Static Pressure (Inches of Water)<br />
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
3-HP Standard Motor & Field Supplied<br />
Low Static Drive (1)<br />
3-HP Standard Motor & Drive<br />
3200 — — 761 1.10 798 1.22 834 1.35 875 1.51 916 1.68 955 1.85 991 2.01 1022 2.16 1050 2.31<br />
3600 799 1.35 836 1.48 872 1.63 904 1.77 936 1.91 972 2.09 1009 2.28 1045 2.47 1079 2.66 1111 2.84<br />
4000 881 1.81 913 1.96 947 2.12 977 2.28 1006 2.44 1035 2.60 1066 2.78 1100 2.99 1133 3.20 1165 3.41<br />
4400 963 2.39 992 2.54 1023 2.71 1052 2.89 1079 3.06 1106 3.23 1132 3.41 1160 3.61 1189 3.82 1219 4.05<br />
4800 1045 3.07 1072 3.23 1099 3.41 1127 3.61 1154 3.80 1179 3.98 1203 4.17 1227 4.36 1251 4.56 1278 4.80<br />
5-HP Oversized Motor & Drive<br />
Table PD-52 — Continued<br />
External Static Pressure (Inches of Water)<br />
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive<br />
3200 1077 2.45 1103 2.60 1126 2.73 1150 2.87 1171 3.01 1193 3.15 1214 3.29 1233 3.42 1253 3.56 1274 3.71<br />
3600 1140 3.02 1165 3.18 1190 3.34 1214 3.51 1235 3.66 1257 3.82 1279 3.98 1298 4.13 1317 4.28 1338 4.45<br />
4000 1196 3.62 1225 3.83 1252 4.03 1276 4.22 1299 4.40 1321 4.58 1342 4.76 1363 4.94 1383 5.11 1401 5.28<br />
4400 1250 4.28 1280 4.52 1307 4.75 1334 4.98 1359 5.20 1384 5.43 1405 5.62 — — — — — —<br />
4800 1305 5.03 1334 5.28 1361 5.54 — — — — — — — — — — — — — —<br />
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />
Notes:<br />
Data includes pressure drop due to standard filters and wet coils.<br />
No accessories or options are included in pressure drop data.<br />
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.<br />
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.<br />
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.<br />
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />
Table PD-53 — Belt Drive Evaporator Fan Performance — 10 Ton — YSC120A3,A4,AW, AK *H— High Heat — Horizontal Airflow<br />
External Static Pressure (Inches of Water)<br />
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
3-HP Standard Motor & Field Supplied<br />
Low Static Drive (1)<br />
3-HP Standard Motor & Drive<br />
3200 768 1.12 805 1.25 842 1.38 884 1.54 924 1.71 962 1.88 998 2.04 1028 2.19 1055 2.34 1082 2.48<br />
3600 856 1.56 888 1.70 921 1.84 955 2.00 992 2.19 1028 2.37 1063 2.57 1096 2.75 1126 2.93 1153 3.10<br />
4000 943 2.10 973 2.26 1002 2.41 1031 2.58 1062 2.76 1096 2.96 1129 3.17 1161 3.38 1192 3.59 1222 3.81<br />
4400 1031 2.76 1060 2.94 1086 3.11 1113 3.28 1139 3.45 1167 3.66 1198 3.89 1228 4.11 1257 4.34 1287 4.58<br />
4800 1119 3.45 1146 3.74 1171 3.93 1195 4.11 1219 4.30 1243 4.50 1270 4.72 1297 4.96 1325 5.21 1353 5.46<br />
5-HP Oversized Motor & Drive<br />
Table PD-53 — Continued<br />
External Static Pressure (Inches of Water)<br />
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive<br />
3200 1107 2.62 1131 2.76 1154 2.90 1176 3.04 1197 3.17 1218 3.32 1238 3.46 1257 3.59 1276 3.73 1296 3.87<br />
3600 1178 3.27 1202 3.42 1224 3.58 1247 3.74 1268 3.90 1288 4.05 1308 4.21 1328 4.37 1346 4.52 1366 4.69<br />
4000 1249 4.01 1273 4.19 1296 4.38 1318 4.56 1339 4.73 1361 4.91 1380 5.08 1399 5.26 1418 5.44 — —<br />
4400 1315 4.81 1340 5.03 1366 5.26 1389 5.48 1410 5.67 — — — — — — — — — —<br />
4800 1379 5.71 — — — — — — — — — — — — — — — — — —<br />
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />
Notes:<br />
Data includes pressure drop due to standard filters and wet coils.<br />
No accessories or options are included in pressure drop data.<br />
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.<br />
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.<br />
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.<br />
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />
55