52<br />

Performance<br />

Data<br />

(8½ Ton)<br />

Standard Efficiency<br />

Table PD-46 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —DownflowAirflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2720 — — — — 608 0.59 649 0.70 689 0.82 728 0.94 764 1.06 798 1.19 829 1.33 859 1.46<br />

3060 — — 615 0.65 654 0.75 692 0.87 728 0.99 764 1.13 799 1.26 833 1.39 864 1.53 894 1.68<br />

3400 625 0.72 665 0.83 702 0.95 736 1.06 770 1.19 804 1.34 836 1.49 868 1.63 899 1.78 928 1.93<br />

3740 681 0.93 716 1.05 752 1.18 784 1.31 815 1.44 846 1.58 876 1.74 906 1.90 935 2.06 963 2.22<br />

4080 737 1.19 769 1.31 802 1.45 833 1.60 862 1.73 891 1.87 919 2.03 947 2.20 974 2.37 1001 2.55<br />

Table PD-46 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

2720 888 1.61 916 1.76 943 1.91 970 2.07 996 2.22 1021 2.37 1046 2.53 1071 2.69 1096 2.86 1119 3.02<br />

3060 922 1.82 949 1.98 976 2.14 1001 2.31 1026 2.47 1051 2.65 1074 2.81 1098 2.99 1120 3.16 1144 3.34<br />

3400 957 2.08 984 2.24 1011 2.41 1035 2.58 1060 2.75 1083 2.93 1106 3.11 1128 3.29 — — — —<br />

3740 992 2.39 1018 2.55 1045 2.72 1070 2.90 1095 3.08 1117 3.25 1140 3.44 — — — — — —<br />

4080 1028 2.73 1053 2.90 1079 3.07 1104 3.26 1128 3.44 — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-47 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *H— High Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2720 — — — — 619 0.62 661 0.74 700 0.85 738 0.97 773 1.09 807 1.23 838 1.36 868 1.51<br />

3060 586 0.58 629 0.68 667 0.79 705 0.91 741 1.04 776 1.17 810 1.30 843 1.44 874 1.58 904 1.72<br />

3400 642 0.76 681 0.88 717 1.00 751 1.12 785 1.25 817 1.40 849 1.55 881 1.69 911 1.84 940 1.99<br />

3740 698 0.99 735 1.12 769 1.25 800 1.37 831 1.51 862 1.66 892 1.82 920 1.98 950 2.14 977 2.30<br />

4080 756 1.26 789 1.40 821 1.54 851 1.68 879 1.82 908 1.97 936 2.13 964 2.30 991 2.48 1017 2.66<br />

Table PD-47 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

2720 896 1.65 923 1.80 950 1.95 977 2.11 1003 2.26 1029 2.42 1053 2.57 1078 2.74 1102 2.90 1124 3.06<br />

3060 932 1.88 959 2.04 985 2.20 1010 2.36 1034 2.53 1058 2.70 1082 2.87 1105 3.05 1129 3.22 1151 3.39<br />

3400 969 2.15 996 2.31 1020 2.48 1045 2.65 1070 2.83 1093 3.00 1116 3.19 1138 3.37 — — — —<br />

3740 1005 2.47 1032 2.64 1058 2.81 1083 2.99 1106 3.16 1129 3.35 — — — — — — — —<br />

4080 1044 2.83 1069 3.01 1095 3.19 1119 3.37 — — — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop<br />

due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

RT-PRC006-EN