Performance<br />

Data<br />

(3 Ton)<br />

Standard Efficiency<br />

Table PD-22 — Belt Drive Evaporator Fan Performance — 3 Ton — YSC036A3,A4,AW*L, M — Low and Medium Heat — Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60<br />

1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69<br />

1200 645 0.22 720 0.28 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79<br />

1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 1135 0.89<br />

1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00<br />

Table PD-22 — Continued<br />

1-HP Standard Motor & Field Supplied High Static Drive (2)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Drive<br />

960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90<br />

1080 1090 0.75 1123 0.81 1154 0.87 1185 0.93 1215 0.99<br />

1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12<br />

1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26<br />

1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41<br />

1-HP Standard Motor &<br />

Field Supplied High Static Drive (2)<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.<br />

2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate<br />

reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular<br />

data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-23 — Belt Drive Evaporator Fan Performance — 3 Ton — YSC036A3,A4,AW*H — High Heat — Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60<br />

1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70<br />

1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80<br />

1320 711 0.29 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90<br />

1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02<br />

Table PD-23 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard<br />

1-HP Standard Motor & Field<br />

Motor & Drive<br />

Supplied High Static Drive (2)<br />

960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90<br />

1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00<br />

1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13<br />

1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28<br />

1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43<br />

1-HP Standard Motor & Field SuppliedHigh Static Drive (2)<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.<br />

2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

RT-PRC006-EN