RT-PRC006-EN<br />

Performance<br />

Data<br />

(5 Ton)<br />

Standard Efficiency<br />

Table PD-28 — Belt Drive Evaporator Fan Performance — 5 Ton — YSC060A3,A4,AW *L,M — Low and Medium Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1600 747 0.40 797 0.46 846 0.51 893 0.57 938 0.64 981 0.72 1020 0.79 1056 0.85 1091 0.92 1125 0.99<br />

1800 828 0.56 873 0.62 917 0.68 960 0.74 1002 0.81 1042 0.89 1081 0.97 1118 1.05 1152 1.13 1185 1.20<br />

2000 909 0.75 951 0.82 992 0.89 1031 0.95 1069 1.01 1107 1.09 1144 1.18 1179 1.27 1213 1.37 1246 1.45<br />

2200 992 0.98 1031 1.06 1068 1.13 1104 1.20 1139 1.27 1175 1.35 1209 1.43 — — — — — —<br />

2400 1075 1.26 1111 1.34 1145 1.42 1179 1.50 — — — — — — — — — — — —<br />

Table PD-28 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Drive<br />

1600 1158 1.05 1190 1.13 1221 1.20 1251 1.27 1281 1.35<br />

1800 1216 1.28 1246 1.35 1276 1.43 — — — —<br />

2000 — — — — — — — — — —<br />

2200 — — — — — — — — — —<br />

2400 — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop<br />

due to other options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be<br />

necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose<br />

motors, specifically designed and tested to operate reliably and<br />

continuously at all cataloged conditions. Using the full horsepower<br />

range of our fan motors as shown in our tabular data will not result in<br />

nuisance tripping or premature motor failure. Our product’s warranty<br />

will not be affected.<br />

Table PD-29 — Belt Drive Evaporator Fan Performance — 5 Ton — YSC060A3,A4,AW *H — High Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1600 764 0.42 814 0.47 862 0.53 909 0.60 953 0.67 994 0.74 1032 0.81 1069 0.88 1103 0.94 1136 1.01<br />

1800 848 0.58 892 0.65 936 0.70 978 0.77 1020 0.84 1059 0.92 1098 1.01 1132 1.09 1166 1.16 1198 1.24<br />

2000 932 0.79 973 0.86 1013 0.92 1051 0.98 1090 1.06 1127 1.14 1163 1.23 1197 1.32 1231 1.42 1262 1.50<br />

2200 1017 1.03 1055 1.11 1091 1.18 1127 1.25 1162 1.32 1196 1.40 1231 1.49 — — — — — —<br />

2400 1103 1.32 1138 1.41 1171 1.49 — — — — — — — — — — — — — —<br />

Table PD-29 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Drive<br />

1600 1168 1.08 1201 1.15 1231 1.22 1261 1.30 1290 1.37<br />

1800 1229 1.31 1259 1.39 1288 1.46 — — — —<br />

2000 — — — — — — — — — —<br />

2200 — — — — — — — — — —<br />

2400 — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop<br />

due to other options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may<br />

be necessary.<br />

Factory supplied motors, in commercial equipment, are definite<br />

purpose motors, specifically designed and tested to operate reliably<br />

and continuously at all cataloged conditions. Using the full horsepower<br />

range of our fan motors as shown in our tabular data will not result in<br />

nuisance tripping or premature motor failure. Our product’s warranty<br />

will not be affected.<br />