26.03.2013 Views

Packaged Gas/Electric Rooftop Units - Trane

Packaged Gas/Electric Rooftop Units - Trane

Packaged Gas/Electric Rooftop Units - Trane

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

RT-PRC006-EN<br />

Performance<br />

Data<br />

(7½ Ton)<br />

Standard Efficiency<br />

Table PD-44 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW *M — Medium Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41<br />

2700 756 0.79 795 0.87 841 0.97 884 1.08 923 1.18 959 1.27 992 1.36 1025 1.47 1057 1.58 1089 1.70<br />

3000 833 1.07 865 1.16 906 1.25 946 1.36 985 1.49 1020 1.61 1052 1.71 1083 1.81 1114 1.91 1143 2.03<br />

3300 910 1.41 938 1.50 972 1.60 1010 1.70 1047 1.84 1081 1.97 1114 2.11 1144 2.22 1173 2.33 1200 2.44<br />

3600 988 1.81 1014 1.91 1042 2.01 1076 2.12 1110 2.25 1143 2.39 1175 2.54 1205 2.69 1234 2.82 1260 2.94<br />

3-HP Oversized Motor & Drive<br />

2-HP Standard Motor & High Static Drive (or 3-HP Oversized Motor)<br />

Table PD-44 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor 2-HP Standard Motor & High Static Drive Kit<br />

& Drive (or 3-HP Oversized Motor & Drive)<br />

2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 1325 2.40 1353 2.52<br />

2700 1120 1.82 1152 1.93 1183 2.05 1214 2.17 1243 2.28 1273 2.40 1302 2.52 1330 2.64 1357 2.76 1385 2.89<br />

3000 1172 2.15 1201 2.29 1229 2.42 1257 2.55 1285 2.68 1312 2.80 1340 2.93 1367 3.06 1395 3.19 1421 3.33<br />

3300 1227 2.56 1255 2.69 1281 2.83 1307 2.97 1333 3.11 1359 3.26 1384 3.40 — — — — — —<br />

3600 1287 3.06 1312 3.18 1337 3.31 1361 3.45 — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.<br />

Table PD-45 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW, AK *H— High Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2400 713 0.62 764 0.71 811 0.81 851 0.89 889 0.97 926 1.07 962 1.17 997 1.28 1031 1.38 1067 1.48<br />

2700 790 0.86 837 0.96 880 1.07 919 1.17 955 1.26 989 1.36 1022 1.46 1054 1.57 1086 1.69 1117 1.80<br />

3000 869 1.16 910 1.26 950 1.38 989 1.50 1023 1.62 1056 1.72 1086 1.82 1116 1.92 1146 2.04 1175 2.17<br />

3300 949 1.53 985 1.63 1023 1.75 1058 1.88 1092 2.02 1124 2.15 1154 2.26 1182 2.37 1210 2.48 1237 2.60<br />

3600 1029 1.97 1061 2.07 1096 2.19 1130 2.33 1162 2.48 1193 2.63 1222 2.77 1250 2.89 1276 3.01 1302 3.13<br />

Table PD-45 — Continued<br />

3-HP Oversized Motor & Drive<br />

2-HP Standard Motor & High Static Drive (or 3-HP Oversized Motor)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard 2-HP Standard Motor & High Static Drive Kit<br />

Motor & Drive (or 3-HP Oversized Motor & Drive)<br />

2400 1101 1.59 1134 1.69 1166 1.80 1197 1.90 1229 2.02 1259 2.13 1287 2.25 1317 2.37 1344 2.48 1373 2.61<br />

2700 1148 1.92 1180 2.04 1210 2.15 1241 2.27 1269 2.39 1299 2.51 1326 2.62 1354 2.74 1383 2.88 1409 3.00<br />

3000 1204 2.30 1232 2.43 1260 2.56 1287 2.69 1316 2.82 1344 2.95 1370 3.07 1397 3.20 1423 3.34 — —<br />

3300 1264 2.74 1290 2.87 1316 3.02 1342 3.16 1367 3.30 1393 3.45 — — — — — — — —<br />

3600 1327 3.26 1352 3.39 — — — — — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750..<br />

1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our tabular<br />

data will not result in nuisance tripping or premature motor failure. Our product’s<br />

warranty will not be affected.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our tabular<br />

data will not result in nuisance tripping or premature motor failure. Our product’s<br />

warranty will not be affected.<br />

51

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!