50<br />

Performance<br />

Data<br />

(7½ Ton)<br />

Standard Efficiency<br />

Table PD-42 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW, AK *H — High Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2400 — — 697 0.62 745 0.71 790 0.80 830 0.89 869 0.98 906 1.07 941 1.16 976 1.26 1009 1.36<br />

2700 717 0.74 760 0.83 804 0.93 847 1.03 887 1.13 922 1.23 958 1.33 991 1.43 1024 1.53 1055 1.64<br />

3000 787 0.99 826 1.09 865 1.20 905 1.31 943 1.42 979 1.54 1012 1.64 1044 1.76 1075 1.87 1105 1.98<br />

3300 858 1.30 894 1.41 929 1.52 965 1.64 1001 1.77 1036 1.89 1068 2.01 1099 2.13 1129 2.25 1157 2.37<br />

3600 930 1.66 963 1.78 995 1.90 1028 2.03 1061 2.16 1093 2.30 1126 2.43 1157 2.57 1185 2.70 1212 2.83<br />

3-HP Oversized Motor & Drive<br />

2-HP Standard Motor & High Static Drive (or 3-HP Oversized Motor)<br />

Table PD-42 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor & Drive)<br />

2400 1042 1.46 1073 1.56 1104 1.67 1134 1.77 1163 1.87 1190 1.97 1218 2.08 1244 2.18 1271 2.28 1296 2.38<br />

2700 1086 1.75 1117 1.86 1146 1.97 1174 2.09 1203 2.21 1230 2.32 1255 2.44 1282 2.55 1308 2.67 1333 2.78<br />

3000 1134 2.09 1163 2.21 1191 2.33 1218 2.45 1245 2.58 1272 2.70 1298 2.83 1323 2.96 1348 3.09 1372 3.22<br />

3300 1185 2.49 1212 2.61 1238 2.74 1265 2.87 1292 3.01 1316 3.13 1341 3.27 1366 3.41 — — — —<br />

3600 1239 2.96 1265 3.09 1290 3.22 1316 3.36 — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically<br />

designed and tested to operate reliably and continuously at all cataloged conditions. Using the<br />

full horsepower range of our fan motors as shown in our tabular data will not result in<br />

nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-43 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW, AK *L— Low Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2400 653 0.53 694 0.59 745 0.67 793 0.77 835 0.86 874 0.94 911 1.03 948 1.13 982 1.23 1017 1.34<br />

2700 725 0.73 760 0.80 801 0.88 847 0.98 889 1.09 927 1.19 963 1.28 997 1.38 1030 1.48 1061 1.60<br />

3000 798 0.98 830 1.06 862 1.15 902 1.24 943 1.35 981 1.48 1017 1.60 1050 1.70 1081 1.80 1111 1.90<br />

3300 872 1.28 901 1.38 929 1.47 961 1.56 998 1.67 1036 1.80 1071 1.93 1104 2.07 1135 2.19 1164 2.30<br />

3600 946 1.65 973 1.75 1000 1.85 1025 1.95 1057 2.06 1091 2.17 1125 2.31 1158 2.46 1189 2.61 1219 2.75<br />

3-HP Oversized Motor & Drive<br />

Table PD-43 — Continued<br />

2-HP Standard Motor & High Static Drive (or 3-HP Oversized Motor)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor & Drive)<br />

2400 1053 1.44 1087 1.55 1121 1.65 1153 1.76 1185 1.86 1217 1.98 1246 2.08 1277 2.20 1306 2.32 1334 2.44<br />

2700 1093 1.71 1124 1.83 1156 1.95 1187 2.06 1218 2.18 1248 2.30 1277 2.42 1306 2.53 1333 2.65 1361 2.78<br />

3000 1141 2.02 1170 2.15 1198 2.28 1227 2.41 1255 2.54 1283 2.67 1311 2.79 1339 2.93 1365 3.05 1391 3.18<br />

3300 1192 2.41 1220 2.52 1247 2.65 1272 2.78 1299 2.92 1325 3.07 1350 3.21 1376 3.36 — — — —<br />

3600 1246 2.87 1272 2.99 1298 3.11 1323 3.24 1348 3.37 — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop<br />

due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our tabular<br />

data will not result in nuisance tripping or premature motor failure. Our product’s<br />

warranty will not be affected.<br />

RT-PRC006-EN