RT-PRC006-EN<br />

Performance<br />

Data<br />

(4 Ton)<br />

Standard Efficiency<br />

Table PD-24 — Belt Drive Evaporator Fan Performance — 4 Ton — YSC048A3,A4,AW*L,M — Low and Medium Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1280 604 0.21 666 0.25 724 0.30 778 0.36 826 0.41 870 0.47 911 0.52 952 0.58 990 0.63 1026 0.69<br />

1440 665 0.29 720 0.34 773 0.38 824 0.44 872 0.51 916 0.57 956 0.63 994 0.69 1030 0.75 1065 0.81<br />

1600 726 0.38 777 0.44 826 0.49 873 0.54 919 0.61 961 0.68 1002 0.75 1039 0.82 1074 0.89 1109 0.95<br />

1760 789 0.50 836 0.56 881 0.61 924 0.67 967 0.73 1008 0.81 1048 0.89 1085 0.97 1120 1.04 1154 1.12<br />

1920 851 0.63 896 0.70 938 0.76 978 0.82 1018 0.88 1057 0.96 1095 1.04 1131 1.13 1167 1.21 1199 1.30<br />

Table PD-24 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Drive<br />

1280 1062 0.76 1097 0.82 1130 0.88 1163 0.95 1195 1.02<br />

1440 1100 0.88 1133 0.94 1166 1.01 1198 1.08 1228 1.15<br />

1600 1141 1.02 1173 1.09 1205 1.16 1235 1.23 1265 1.31<br />

1760 1185 1.19 1215 1.26 1246 1.33 1275 1.41 1304 1.49<br />

1920 1230 1.37 1260 1.45 — — — — — —<br />

1-HP Standard Motor & Field<br />

Supplied High Static Drive (2)<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standardfilters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to<br />

other options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be<br />

necessary.<br />

2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be<br />

necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose<br />

motors, specifically designed and tested to operate reliably and<br />

continuously at all cataloged conditions. Using the full horsepower range<br />

of our fan motors as shown in our tabular data will not result in nuisance<br />

tripping or premature motor failure. Our product’s warranty will not be<br />

affected.<br />

Table PD-25 — Belt Drive Evaporator Fan Performance — 4 Ton — YSC048A3,A4,AW*H — High Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1280 618 0.22 678 0.26 735 0.31 788 0.37 835 0.42 879 0.48 920 0.53 960 0.59 997 0.65 1034 0.71<br />

1440 680 0.30 735 0.35 787 0.40 838 0.46 884 0.52 926 0.59 966 0.64 1004 0.70 1040 0.77 1075 0.83<br />

1600 744 0.40 794 0.45 842 0.50 888 0.56 933 0.64 975 0.71 1015 0.78 1051 0.84 1086 0.91 1120 0.97<br />

1760 808 0.52 854 0.58 899 0.64 941 0.69 984 0.76 1024 0.84 1063 0.92 1099 1.00 1134 1.07 1167 1.14<br />

1920 873 0.66 916 0.73 957 0.79 997 0.85 1037 0.92 1075 0.99 1112 1.08 1148 1.17 1183 1.25 1214 1.33<br />

Table PD-25 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Drive<br />

1280 1069 0.77 1104 0.83 1137 0.90 1169 0.96 1202 1.04<br />

1440 1109 0.89 1142 0.96 1174 1.03 1205 1.10 1236 1.17<br />

1600 1153 1.04 1184 1.11 1214 1.18 1244 1.26 1275 1.33<br />

1760 1197 1.22 1228 1.29 1258 1.36 1287 1.44 — —<br />

1920 1245 1.41 1274 1.49 — — — — — —<br />

1-HP Standard Motor &<br />

Field Supplied High Static Drive (2)<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to<br />

other options/accessories<br />

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be<br />

necessary.<br />

2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be<br />

necessary.<br />

Factory supplied motors, in commercial equipment, are definite purpose<br />

motors, specifically designed and tested to operate reliably and<br />

continuously at all cataloged conditions. Using the full horsepower range of<br />

our fan motors as shown in our tabular data will not result in nuisance<br />

tripping or premature motor failure. Our product’s warranty will not be<br />

affected.<br />