70<br />

Performance<br />

Data<br />

(8½ Ton)<br />

High Efficiency<br />

Table PD-80 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *M — Medium Heat — Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2720 625 0.62 671 0.73 714 0.84 763 0.98 809 1.13 851 1.27 885 1.39 917 1.51 946 1.63 974 1.75<br />

3060 691 0.86 734 0.98 772 1.10 812 1.23 856 1.39 897 1.55 936 1.71 970 1.86 1001 2.00 1028 2.14<br />

3400 759 1.15 798 1.28 835 1.41 868 1.55 904 1.70 943 1.87 982 2.05 1019 2.23 1052 2.41 1082 2.57<br />

3740 827 1.50 863 1.64 898 1.79 930 1.94 960 2.09 994 2.26 1029 2.44 1064 2.64 1098 2.84 1130 3.03<br />

4080 897 1.92 929 2.07 962 2.23 992 2.39 1021 2.55 1049 2.72 1079 2.90 1112 3.10 1144 3.31 — —<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

Table PD-80 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2720 1000 1.87 1025 1.99 1048 2.10 1072 2.22 1095 2.34 1117 2.46 1139 2.58 1161 2.70 1182 2.82 1203 2.95<br />

3060 1054 2.27 1080 2.41 1103 2.53 1126 2.67 1149 2.80 1170 2.93 1192 3.07 1211 3.20 1231 3.33 — —<br />

3400 1108 2.73 1134 2.88 1158 3.03 1181 3.17 1204 3.33 — — — — — — — — — —<br />

3740 1160 3.23 1187 3.41 — — — — — — — — — — — — — — — —<br />

4080 — — — — — — — — — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-81 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H— High Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2720 640 0.66 684 0.77 729 0.89 778 1.03 823 1.17 863 1.31 896 1.43 926 1.55 955 1.67 982 1.79<br />

3060 709 0.91 750 1.03 788 1.15 829 1.29 872 1.45 913 1.61 950 1.77 983 1.92 1011 2.05 1038 2.19<br />

3400 778 1.21 817 1.35 851 1.48 885 1.62 924 1.78 963 1.96 1000 2.14 1035 2.30 1067 2.49 1095 2.65<br />

3740 848 1.58 885 1.73 917 1.88 948 2.03 979 2.18 1014 2.36 1050 2.56 1084 2.76 1118 2.96 1148 3.15<br />

4080 919 2.02 952 2.18 984 2.35 1012 2.50 1041 2.67 1070 2.84 1102 3.04 1135 3.25 — — — —<br />

3-HP Oversized Motor & Drive<br />

Table PD-81 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2720 1007 1.90 1032 2.02 1056 2.14 1079 2.26 1101 2.38 1124 2.50 1146 2.62 1167 2.74 1189 2.86 1209 2.98<br />

3060 1064 2.32 1090 2.46 1113 2.59 1135 2.72 1157 2.85 1178 2.98 1199 3.12 1220 3.26 1240 3.39 — —<br />

3400 1121 2.80 1146 2.95 1170 3.10 1193 3.25 1215 3.40 — — — — — — — — — —<br />

3740 1177 3.34 — — — — — — — — — — — — — — — — — —<br />

4080 — — — — — — — — — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

RT-PRC006-EN