Performance<br />

Data<br />

(8½ Ton)<br />

High Efficiency<br />

Table PD-76— Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L — Low Heat — Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2720 — — — — 621 0.62 662 0.74 703 0.86 741 0.98 777 1.11 810 1.24 841 1.38 871 1.52<br />

3060 587 0.58 630 0.69 668 0.79 707 0.92 743 1.05 779 1.18 814 1.32 846 1.45 878 1.60 907 1.75<br />

3400 643 0.77 683 0.89 718 1.00 753 1.13 787 1.26 820 1.41 853 1.56 884 1.71 915 1.86 944 2.02<br />

3740 699 0.99 736 1.12 770 1.25 802 1.38 833 1.52 864 1.67 894 1.83 925 2.00 953 2.16 982 2.33<br />

4080 757 1.26 790 1.40 823 1.55 853 1.69 882 1.83 910 1.98 938 2.15 967 2.32 994 2.50 1021 2.68<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

Table PD-76 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2720 900 1.67 927 1.82 954 1.97 980 2.12 1006 2.28 1032 2.44 1057 2.60 1082 2.76 1105 2.92 1129 3.09<br />

3060 936 1.90 962 2.06 989 2.22 1014 2.39 1039 2.56 1062 2.73 1085 2.90 1109 3.07 1133 3.25 1155 3.43<br />

3400 973 2.17 999 2.34 1025 2.51 1050 2.68 1074 2.86 1097 3.04 1120 3.22 1142 3.41 — — — —<br />

3740 1010 2.50 1036 2.66 1062 2.84 1087 3.01 1110 3.19 1134 3.39 — — — — — — — —<br />

4080 1047 2.86 1073 3.04 1098 3.22 1123 3.40 — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-77 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *M— Medium Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2720 — — — — 623 0.63 664 0.75 704 0.87 742 0.99 778 1.11 811 1.24 842 1.38 872 1.53<br />

3060 589 0.58 632 0.69 670 0.80 709 0.92 745 1.06 781 1.19 815 1.32 848 1.46 880 1.60 909 1.75<br />

3400 645 0.77 685 0.89 721 1.01 755 1.13 789 1.27 822 1.42 854 1.57 886 1.72 916 1.87 945 2.02<br />

3740 702 1.00 739 1.14 772 1.26 804 1.39 836 1.53 867 1.69 897 1.85 926 2.01 956 2.18 984 2.34<br />

4080 759 1.27 793 1.42 826 1.56 856 1.70 884 1.84 913 2.00 941 2.16 969 2.34 996 2.52 1024 2.70<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

Table PD-77 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2720 900 1.67 928 1.82 955 1.98 982 2.14 1008 2.29 1033 2.45 1057 2.60 1083 2.77 1107 2.94 1129 3.10<br />

3060 936 1.91 964 2.07 989 2.23 1015 2.39 1039 2.56 1063 2.73 1088 2.92 1111 3.09 1134 3.26 1157 3.44<br />

3400 974 2.18 1001 2.35 1027 2.52 1051 2.69 1075 2.87 1098 3.05 1121 3.23 1144 3.42 — — — —<br />

3740 1011 2.50 1038 2.68 1064 2.85 1089 3.03 1113 3.22 1135 3.40 — — — — — — — —<br />

4080 1050 2.87 1076 3.05 1101 3.24 1126 3.43 — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />