Table PD-72 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —DownflowAirflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2400 — — — — — — 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30<br />

2700 — — — — 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 796 1.18 828 1.32 857 1.45<br />

3000 — — 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 792 1.22 826 1.36 858 1.49 888 1.64<br />

3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85<br />

3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10<br />

2-HP Standard Motor & Drive<br />

Table PD-72 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2400 858 1.43 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75<br />

2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00<br />

3000 916 1.79 944 1.94 970 2.10 995 2.26 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27<br />

3300 947 2.01 974 2.16 1000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38 — —<br />

3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30 — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-73 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —DownflowAirflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2400 — — — — — — 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32<br />

2700 — — — — 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 804 1.21 835 1.35 865 1.49<br />

3000 — — 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 804 1.26 837 1.40 868 1.54 897 1.69<br />

3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91<br />

3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17<br />

2-HP Standard Motor & Drive<br />

Table PD-73 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78<br />

2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05<br />

3000 925 1.83 952 1.99 978 2.15 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33<br />

3300 958 2.06 984 2.22 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28 — — — —<br />

3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39 — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

RT-PRC006-EN