Field Installed Options<br />

CO Sensing<br />

2<br />

The CO sensor shall have the ability to<br />

2<br />

monitor space occupancy levels within<br />

the building by measuring the parts per<br />

million of CO (Carbon Dioxide) in the air.<br />

2<br />

As the CO levels increase, the outside air<br />

2<br />

damper modulates to meet the CO2 space ventilation requirements.<br />

Digital Display Zone Sensor<br />

The Digital LCD (Liquid Crystal Display)<br />

zone sensor has the look and functionality<br />

of standard zone sensors. This sensor<br />

includes a digital display of set point<br />

adjustment and space temperature in F<br />

(Fahrenheit) or C (Celsius). Includes FAN<br />

and SYSTEM buttons (supports the<br />

service functions of the standard sensor).<br />

E-squared memory stores last<br />

programmed set points. Requires 24 VAC<br />

(Volts AC). This sensor should be utilized<br />

with ReliaTel controls.<br />

Dual Thermistor Remote Zone Sensor<br />

This sensor will allow the customer to<br />

reduce the total number of remote<br />

sensors to obtain space temperature<br />

averaging. This sensor should be utilized<br />

with ReliaTel controls.<br />

High Static Drive<br />

The high static drive option shall allow the<br />

standard motor on the 6 and 7½ ton units<br />

to operate with improved external static<br />

capabilities.<br />

Humidity Sensor<br />

This wall-mounted humidity sensor is<br />

used to control activation of the hot gas<br />

reheat dehumidification option. The<br />

humidity sensor can be set for humidity<br />

levels between 40% and 60% relative<br />

humidity by adjusting the ReliaTel Options<br />

Module.<br />

98<br />

Mechanical<br />

Specifications<br />

Humidity Sensor<br />

This duct-mounted humidity sensor is<br />

used to control activation of the hot gas<br />

reheat dehumidification option. The<br />

humidity sensor can be set for humidity<br />

levels between 40% and 60% relative<br />

humidity by adjusting the ReliaTel Options<br />

Module.<br />

Manual Outside Air Damper<br />

This rain hood and screen shall provide<br />

up to 50 percent outside air.<br />

Motorized Outside Air Dampers<br />

Manually set outdoor air dampers shall<br />

provide up to 50 percent outside air. Once<br />

set, outdoor air dampers shall open to set<br />

position when indoor fan starts. The<br />

damper shall close to the full closed<br />

position when indoor fan shuts down.<br />

Powered Exhaust<br />

The powered exhaust, available for 6-10<br />

ton units, shall provide exhaust of return<br />

air, when using an economizer, to<br />

maintain better bulding pressurization.<br />

Remote Potentiometer<br />

The minimum position setting of the<br />

economizer shall be adjusted with this<br />

accessory.<br />

Roof Curb<br />

The roof curb shall be designed to mate<br />

with the unit’s downflow supply and<br />

return and provide support and a water<br />

tight installation when installed properly.<br />

The roof curb design shall allow fieldfabricated<br />

rectangular supply/return<br />

ductwork to be connected directly to the<br />

curb. Curb design shall comply with<br />

NRCA requirements. Curb shall be<br />

shipped knocked down for field assembly<br />

and shall include wood nailer strips.<br />

Thermostat<br />

Two stage heating and cooling operation<br />

or one stage heating and cooling shall be<br />

available in either manual or automatic<br />

changeover. Automatic programmable<br />

electronic with night set back shall also be<br />

available.<br />

Ventilation Override Accessory<br />

With the Ventilation Override Accessory<br />

installed, the unit can be set to transition<br />

up to 3 different pre-programmed<br />

sequences for Smoke Purge,<br />

Pressurization, and Exhaust. The<br />

transition occurs when a binary input on<br />

the RTOM is closed (shorted). This would<br />

typically be a hard wired relay output<br />

from a smoke detector or fire control<br />

panel. The ventilation override accessory<br />

shall be available as field installed.<br />

Zone Sensor<br />

This control shall be provided to interface<br />

with the Micro equipped units and shall<br />

be available in either manual, automatic<br />

programmable with night setback, with<br />

system malfunction lights, or remote<br />

sensor options.<br />

RT-PRC006-EN