ReliaTel Controlled <strong>Units</strong><br />

Zone Sensors are the building<br />

occupant’s comfort control devices for<br />

Precedent units with the Micro control:<br />

Manual Changeover<br />

Heat, Cool or Off System Switch. Fan<br />

Auto or Off Switch.<br />

One temperature<br />

setpoint lever.<br />

Manual/Automatic<br />

Changeover<br />

Auto, Heat, Cool or Off System Switch.<br />

Fan Auto or Off Switch. Two temperature<br />

setpoint levers.<br />

Optional Status<br />

Indication LED<br />

lights, System On,<br />

Heat, Cool, or<br />

Service.<br />

Remote Sensor<br />

Sensor(s) available for all zone sensors to<br />

provide remote<br />

sensing capabilities.<br />

RT-PRC006-EN<br />

Controls<br />

Integrated Comfort TM System<br />

Sensor(s) available with optional<br />

temperature adjustment and override<br />

buttons to provide<br />

central control<br />

through a <strong>Trane</strong><br />

Integrated<br />

Comfort TM system.<br />

Dual Thermistor Remote Zone Sensor<br />

This sensor will allow the customer to<br />

reduce the total number of remote<br />

sensors to obtain space temperature<br />

averaging. This sensor should be utilized<br />

with ReliaTel controls.<br />

Digital Display Zone Sensor<br />

The Digital LCD (Liquid Crystal Display)<br />

zone sensor has the look and functionality<br />

of standard zone<br />

sensors. This sensor<br />

includes a digital<br />

display of set point<br />

adjustment and<br />

space temperature<br />

in F (Fahrenheit) or C<br />

(Celsius). Includes<br />

FAN and SYSTEM<br />

buttons (supports<br />

the service functions<br />

of the standard<br />

sensor). E-squared<br />

memory stores last<br />

programmed set points. Requires 24 VAC<br />

(Volts AC). This sensor should be utilized<br />

with ReliaTel controls.<br />

Programmable Night Setback<br />

Auto or manual changeover with sevenday<br />

programming. Keyboard selection of<br />

Heat, Cool, Fan, Auto, or On. All<br />

programmable sensors have System On,<br />

Heat, Cool, Service LED/indicators as<br />

standard. Night Setback Sensors have<br />

one (1) Occupied, one (1) Un-occupied,<br />

and two (2) Override programs per day.<br />

Humidity Sensor<br />

Field installed, wall-mounted or ductmounted<br />

humidity sensor is used to<br />

control activation of the hot gas reheat<br />

dehumidification<br />

option. The<br />

humidity sensor<br />

can be set for<br />

humidity levels<br />

between 40% and<br />

60% relative<br />

humidity by<br />

adjusting the<br />

ReliaTel Options<br />

Module.<br />

CO 2 Sensing<br />

The CO 2 sensor shall have the ability to<br />

monitor space occupancy levels within<br />

the building by<br />

measuring the<br />

parts per million<br />

of CO 2 (Carbon<br />

Dioxide) in the<br />

air. As the CO 2<br />

levels increase,<br />

the outside air<br />

damper<br />

modulates to<br />

meet the CO 2<br />

space ventilation<br />

requirements.<br />

The CO 2 accessory shall be available as<br />

field installed.<br />