Performance<br />
Data<br />
(5 Ton)<br />
Standard Efficiency<br />
Table PD-30 — Belt Drive Evaporator Fan Performance — 5 Ton — YSC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow<br />
External Static Pressure (Inches of Water)<br />
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
1-HP Standard Motor & Drive<br />
1600 825 0.48 889 0.56 946 0.64 996 0.71 1041 0.79 1084 0.87 1126 0.95 1166 1.03 1204 1.11 1240 1.20<br />
1800 913 0.66 971 0.75 1025 0.84 1074 0.92 1117 1.01 1158 1.09 1197 1.18 1235 1.27 1272 1.36 1307 1.45<br />
2000 1003 0.89 1054 0.98 1105 1.08 1153 1.18 1196 1.27 1235 1.37 1272 1.46 1308 1.50 — — — —<br />
2200 1094 1.16 1140 1.26 1187 1.37 1232 1.48 — — — — — — — — — — — —<br />
2400 1185 1.48 — — — — — — — — — — — — — — — — — —<br />
1-HP Standard Motor & Field Supplied<br />
Low Static Drive (1)<br />
Table PD-30 — Continued<br />
External Static Pressure (Inches of Water)<br />
1.10 1.20 1.30 1.40 1.50<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
1-HP Standard Motor & Drive<br />
1600 1274 1.28 1307 1.37 1338 1.46 — — — —<br />
1800 — — — — — — — — — —<br />
2000 — — — — — — — — — —<br />
2200 — — — — — — — — — —<br />
2400 — — — — — — — — — —<br />
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />
Notes:<br />
Data includes pressure drop due to standard filters and wet coils.<br />
No accessories or options are included in pressure drop data.<br />
Refer to Table PD-89 to determine additional static pressure drop<br />
due to other options/accessories<br />
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be<br />
necessary.<br />
Factory supplied motors, in commercial equipment, are definite purpose motors,<br />
specifically designed and tested to operate reliably and continuously at all<br />
cataloged conditions. Using the full horsepower range of our fan motors as<br />
shown in our tabular data will not result in nuisance tripping or premature motor<br />
failure. Our product’s warranty will not be affected.<br />
Table PD-31 — Belt Drive Evaporator Fan Performance — 5 Ton — YSC060A3,A4,AW *H— High Heat — Horizontal Airflow<br />
External Static Pressure (Inches of Water)<br />
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
1-HP Standard Motor & Drive<br />
1600 847 0.51 910 0.59 964 0.66 1011 0.74 1056 0.82 1098 0.89 1140 0.97 1179 1.06 1217 1.14 1252 1.23<br />
1800 938 0.70 995 0.79 1047 0.87 1093 0.96 1135 1.05 1175 1.13 1213 1.22 1251 1.31 1287 1.40 1323 1.49<br />
2000 1030 0.94 1082 1.03 1131 1.13 1176 1.23 1217 1.32 1255 1.42 1292 1.50 — — — — — —<br />
2200 1123 1.23 1170 1.33 1216 1.44 — — — — — — — — — — — — — —<br />
2400 — — — — — — — — — — — — — — — — — — — —<br />
1-HP Standard Motor & Field Supplied<br />
Low Static Drive (1)<br />
Table PD-31 — Continued<br />
External Static Pressure (Inches of Water)<br />
1.10 1.20 1.30 1.40<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP<br />
1-HP Standard Motor & Drive<br />
1600 1285 1.31 1317 1.40 1348 1.49 — —<br />
1800 — — — — — — — —<br />
2000 — — — — — — — —<br />
2200 — — — — — — — —<br />
2400 — — — — — — — —<br />
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />
Notes:<br />
Data includes pressure drop due to standard filters and wet coils.<br />
No accessories or options are included in pressure drop data.<br />
Refer to Table PD-89 to determine additional static pressure drop<br />
due to other options/accessories<br />
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />
Factory supplied motors, in commercial equipment, are definite purpose<br />
motors, specifically designed and tested to operate reliably and continuously<br />
at all cataloged conditions. Using the full horsepower range of our fan motors<br />
as shown in our tabular data will not result in nuisance tripping or premature<br />
motor failure. Our product’s warranty will not be affected.<br />
RT-PRC006-EN