RT-PRC006-EN<br />

Performance<br />

Data<br />

(8½ Ton)<br />

High Efficiency<br />

Table PD-78 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H — High Heat — Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2720 — — 590 0.55 633 0.66 674 0.77 713 0.89 750 1.01 786 1.14 818 1.28 850 1.42 879 1.56<br />

3060 602 0.62 643 0.72 682 0.83 719 0.96 756 1.09 791 1.23 825 1.36 857 1.50 889 1.65 917 1.80<br />

3400 660 0.82 698 0.94 733 1.05 767 1.18 801 1.32 834 1.48 866 1.62 897 1.77 927 1.92 956 2.08<br />

3740 718 1.06 754 1.19 787 1.32 818 1.45 849 1.60 880 1.76 910 1.92 939 2.08 968 2.24 996 2.41<br />

4080 777 1.35 811 1.49 841 1.63 870 1.77 899 1.92 928 2.08 956 2.26 983 2.43 1011 2.61 1037 2.79<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

Table PD-78 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2720 907 1.71 934 1.86 960 2.01 987 2.17 1014 2.33 1039 2.48 1063 2.64 1088 2.81 1112 2.97 1134 3.13<br />

3060 945 1.95 971 2.11 997 2.28 1022 2.45 1047 2.62 1070 2.79 1094 2.96 1117 3.14 1141 3.31 — —<br />

3400 985 2.24 1010 2.40 1036 2.58 1060 2.76 1084 2.93 1106 3.11 1130 3.31 — — — — — —<br />

3740 1023 2.58 1049 2.75 1075 2.93 1099 3.11 1122 3.29 — — — — — — — — — —<br />

4080 1063 2.96 1089 3.15 1114 3.34 — — — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-79 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L— Low Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2720 622 0.62 669 0.73 711 0.84 760 0.97 807 1.12 849 1.26 884 1.38 915 1.50 944 1.62 972 1.74<br />

3060 688 0.85 732 0.97 770 1.09 809 1.22 853 1.38 895 1.54 934 1.70 968 1.85 998 1.99 1026 2.13<br />

3400 756 1.14 795 1.27 832 1.40 866 1.54 901 1.69 941 1.86 979 2.04 1015 2.22 1049 2.40 1079 2.56<br />

3740 824 1.49 859 1.62 895 1.78 926 1.92 957 2.07 990 2.24 1025 2.42 1061 2.62 1095 2.82 1127 3.02<br />

4080 893 1.90 925 2.05 958 2.21 988 2.37 1017 2.53 1046 2.70 1075 2.88 1108 3.08 1140 3.29 — —<br />

2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive<br />

Table PD-79 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2720 998 1.86 1024 1.98 1047 2.10 1071 2.22 1094 2.33 1115 2.45 1138 2.57 1159 2.69 1181 2.82 1201 2.94<br />

3060 1053 2.26 1078 2.39 1102 2.53 1125 2.66 1146 2.79 1169 2.93 1190 3.06 1210 3.19 1230 3.32 1250 3.45<br />

3400 1106 2.71 1131 2.86 1156 3.02 1179 3.16 1201 3.31 1223 3.45 — — — — — — — —<br />

3740 1158 3.21 1185 3.39 — — — — — — — — — — — — — — — —<br />

4080 — — — — — — — — — — — — — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />