Performance<br />

Data<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750<br />

1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.<br />

(7½ Ton)<br />

Standard Efficiency<br />

Table PD-40 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW, AK *L — Low Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

2-HP Standard Motor & Drive<br />

2400 — — — — 676 0.59 726 0.67 773 0.77 815 0.85 854 0.94 891 1.03 928 1.12 963 1.22<br />

2700 — — 682 0.68 727 0.76 770 0.85 814 0.95 856 1.06 895 1.16 931 1.25 965 1.35 998 1.45<br />

3000 693 0.79 738 0.89 780 0.97 819 1.07 858 1.18 898 1.29 936 1.40 972 1.52 1006 1.63 1038 1.73<br />

3300 753 1.03 795 1.14 834 1.23 871 1.33 906 1.45 942 1.56 978 1.69 1014 1.81 1048 1.94 1080 2.06<br />

3600 814 1.31 853 1.44 890 1.55 925 1.65 958 1.76 991 1.88 1023 2.01 1057 2.14 1088 2.28 1121 2.41<br />

Table PD-40 — Continued<br />

3-HP Oversized Motor<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2- HP Standard Motor & Drive 2-HP Standard Motor & High Static DriveKit (or 3-HP Oversized Motor & Drive)<br />

2400 996 1.32 1028 1.42 1061 1.52 1092 1.63 1122 1.73 1151 1.83 1180 1.93 1207 2.03 1235 2.14 1261 2.24<br />

2700 1031 1.56 1062 1.66 1093 1.78 1123 1.89 1153 2.00 1181 2.12 1209 2.23 1236 2.35 1262 2.47 1288 2.58<br />

3000 1070 1.85 1099 1.95 1128 2.07 1158 2.19 1185 2.31 1213 2.43 1240 2.55 1267 2.68 1293 2.81 1319 2.94<br />

3300 1110 2.18 1139 2.29 1167 2.42 1195 2.54 1222 2.66 1248 2.79 1274 2.92 1301 3.05 1325 3.18 1351 3.33<br />

3600 1151 2.55 1181 2.68 1208 2.81 1236 2.95 1261 3.07 1287 3.21 1311 3.33 — — — — — —<br />

3-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.<br />

1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our tabular<br />

data will not result in nuisance tripping or premature motor failure. Our product’s<br />

warranty will not be affected.<br />

Table PD-41 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW *M— Medium Heat —Downflow Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive<br />

2400 — — 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29<br />

2700 676 0.67 721 0.75 764 0.84 809 0.94 851 1.04 891 1.14 927 1.24 961 1.34 994 1.44 1027 1.54<br />

3000 741 0.89 783 0.98 822 1.08 861 1.19 901 1.30 939 1.41 975 1.52 1009 1.64 1041 1.74 1071 1.85<br />

3300 807 1.17 846 1.26 882 1.37 917 1.48 953 1.60 989 1.72 1024 1.85 1058 1.97 1089 2.09 1119 2.21<br />

3600 874 1.50 910 1.60 944 1.71 976 1.83 1008 1.95 1041 2.08 1074 2.22 1107 2.35 1138 2.49 1168 2.62<br />

3-HP Oversized Motor<br />

& Drive<br />

Table PD-41 — Continued<br />

2-HP Standard Motor & High Static Drive (or 3-HP Oversized Motor)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

2-HP Standard Motor & Drive<br />

2-HP Standard Motor & High Static Drive Kit<br />

(or 3-HP Oversized Motor & Drive)<br />

2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 1278 2.31<br />

2700 1058 1.65 1089 1.76 1120 1.87 1149 1.99 1178 2.10 1205 2.21 1232 2.33 1259 2.45 1284 2.56 1310 2.68<br />

3000 1101 1.96 1131 2.08 1160 2.20 1187 2.31 1215 2.44 1243 2.57 1269 2.69 1295 2.82 1321 2.95 1346 3.08<br />

3300 1147 2.33 1176 2.45 1204 2.58 1230 2.70 1256 2.82 1282 2.96 1308 3.09 1333 3.23 1358 3.36 — —<br />

3600 1196 2.75 1223 2.88 1250 3.02 1276 3.15 1301 3.28 1325 3.41 — — — — — — — —<br />

3-HP Oversized Motor & Drive<br />

Factory supplied motors, in commercial equipment, are definite purpose motors,<br />

specifically designed and tested to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan motors as shown in our tabular<br />

data will not result in nuisance tripping or premature motor failure. Our product’s<br />

warranty will not be affected.<br />

49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!